Appendix 4 Buffer Memory Areas
Module information
Module information of FX5-8AD is stored. For module information, 61E0H (fixed hexadecimal value) is stored.
■
Buffer memory address
The following shows the buffer memory address of this area.
Module information [FX2N Allocation Mode]
The FX5-8AD module information in FX2N allocation mode function is stored. For model information, 61E4H (fixed
hexadecimal value) is stored.
■
Buffer memory address
The following shows the buffer memory address of this area.
Firmware version
Firmware version is stored. Firmware version is stored in 4 digit decimal number.
■
Buffer memory address
The following shows the buffer memory address of this area.
Warning output flag (Process alarm upper limit)
The upper limit alarm of the process alarm can be checked for each channel.
■
Buffer memory address
The following shows the buffer memory address of this area.
■
Alert output flag status
• If the limit specified by the process alarm upper upper limit value is equal to or exceeded, Alarm ON (1) is stored in 'Alert
output flag (Process alarm upper limit)' (Un\G36) of the corresponding channel.
• If an alert is detected even in one channel, of the channels where conversion is enabled and the alert output setting
(Process alarm) is enabled, 'Alert output signal' (Un\G69, b8) also turns on.
■
Clearing Alert output flag
• When the digital operation value becomes smaller than the process alarm upper lower limit value, the flag is automatically
cleared.
• Turning off
→
on
→
off 'Operating condition setting request' (Un\G70, b9) allows the flag to be cleared.
Buffer memory name
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
Module information
30
Buffer memory name
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
Module information (in FX2N allocation mode function)
30
Buffer memory name
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
Firmware version
31
Firmware version (in FX2N allocation mode function)
31
(1) 0: Normal, 1: Alarm ON
(2) The values of b8 to b15 are fixed to 0.
Buffer memory name
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
Warning output flag (Process alarm upper limit)
36
0
0
0
0
0
0
0
0
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
b15 b14 b13 b12 b11 b10 b9
b8
b7
b6
b5
b0
b1
b2
b3
b4
(1)
(2)