APPX
Appendix 4 Buffer Memory Areas
169
A
CH1 Input type/range setting
This area is for setting an input type and range setting.
A channel where the set value is other than the above causes an input type/range setting range error (error code: 190
H).
■
Buffer memory address
The following shows the buffer memory address of this area.
■
Enabling the setting
Turn off
→
on
→
off 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■
Default value
The default value is conversion disabled (000FH).
Setting value (Hexadecimal)
Input type
Input range
000FH
Conversion disable
0003H
Current
4 to 20 mA
0010H
0 to 20 mA
0006H
-20 to +20 mA
0011H
Voltage
1 to 5 V
0012H
0 to 5 V
0000H
-10 to +10 V
0013H
0 to 10 V
0014H
Resistance temperature detector
Pt100
0015H
Ni100
0016H
Thermocouple
Thermocouple B
0017H
Thermocouple R
0018H
Thermocouple S
0009H
Thermocouple K
000AH
Thermocouple J
000BH
Thermocouple T
Buffer memory name
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH
Setting Input type/range
598
798
998
1198
1398
1598
1798
1998
Summary of Contents for MELSEC iQ-F
Page 1: ...MELSEC iQ F FX5 User s Manual Analog Control Intelligent function module ...
Page 2: ......
Page 9: ...7 MEMO ...
Page 181: ......