Appendix 4 Buffer Memory Areas
163
A
CH1 Logging data setting
Determine the target to be collected: digital output value or digital operation value.
For details on the logging function, refer to the following.
Setting a value other than the above causes a logging data setting range error (error code: 1D3
H).
When 'CH1 Logging enable/disable setting' (Un\G535) is set to Disable (1), the setting for 'CH1 Logging data setting'
(Un\G536) is ignored.
■
Buffer memory address
The following shows the buffer memory address of this area.
■
Enabling the setting
Turn off
→
on
→
off 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■
Default value
The default value is Digital operation value (1).
CH1 Logging cycle setting value
Set a cycle for storing the logging data.
For details on the logging function, refer to the following.
■
Buffer memory address
The following shows the buffer memory address of this area.
■
Setting range
The setting range varies depending on the setting in 'CH1 Logging cycle unit setting' (Un\G538) and 'CH1 Input type/range
setting' (Un\G598).
• Setting a value out of the above range causes a logging cycle setting value range error (error code: 1D1
H). Logging
cannot be performed.
• If the set logging cycle is below the update cycle of data to be logged, a logging cycle setting disable error (error code:
1D2
H) occurs. Logging cannot be performed.
■
Enabling the setting
Turn off
→
on
→
off 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■
Default value
The default value is set to 1.
Setting value
Setting content
0
Digital output value
1
Digital operation value
Buffer memory name
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH
Logging data setting
536
736
936
1136
1336
1536
1736
1936
CH
Logging data setting (in FX2N allocation mode function)
9171
9172
9173
9174
9175
9176
9177
9178
Buffer memory name
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH
Logging cycle setting value
537
737
937
1137
1337
1537
1737
1937
CH
Logging cycle setting value (In FX2N allocation mode
function)
9181
9182
9183
9184
9185
9186
9187
9188
CH1 Logging cycle unit setting (Un\G538)
CH1 Input type/range setting (Un\G598)
Setting range
ms (1)
Current/Voltage
1 to 32767
Resistance temperature detector/thermocouple
40 to 32767
s (2)
1 to 3600