124
APPX
Appendix 4 Buffer Memory Areas
Warning output flag (Rate alarm upper limit)
The upper limit alarm of the rate alarm can be checked for each channel.
■
Buffer memory address
The following shows the buffer memory address of this area.
■
Alert output flag status
• If the limit specified in the rate alarm upper limit value is equal to or exceeded, Alarm ON (1) is stored in 'Alert output flag
(Rate alarm upper limit)' (Un\G38) of the corresponding channel.
• If an alert is detected even in one channel, of the channels where conversion is enabled and the alert output setting (Rate
alarm) is enabled, 'Alert output signal' (Un\G69, b8) also turns on.
■
Clearing Alert output flag
• When the digital output value becomes smaller than the rate alarm upper limit value, the flag is automatically cleared.
• Turning off
→
on
→
off 'Operating condition setting request' (Un\G70, b9) allows the flag to be cleared.
Warning output flag (Rate alarm lower limit)
The lower limit alarm of the rate alarm can be checked for each channel.
■
Buffer memory address
The following shows the buffer memory address of this area.
■
Alert output flag status
• When the value becomes equal to or smaller than the range specified in the rate alarm lower limit value, Alarm ON (1) is
stored in 'Alert output flag (Rate alarm lower limit)' (Un\G39) corresponding to each channel.
• If an alert is detected even in one channel, of the channels where conversion is enabled and the alert output setting (Rate
alarm) is enabled, 'Alert output signal' (Un\G69, b8) also turns on.
■
Clearing Alert output flag
• When the digital output value becomes smaller than the rate alarm lower limit value, the flag is automatically cleared.
• Turning off
→
on
→
off 'Operating condition setting request' (Un\G70, b9) allows the flag to be cleared.
(1) 0: Normal, 1: Alarm ON
(2) The values of b8 to b15 are fixed to 0.
Buffer memory name
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
Warning output flag (Rate alarm upper limit)
38
(1) 0: Normal, 1: Alarm ON
(2) The values of b8 to b15 are fixed to 0.
Buffer memory name
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
Warning output flag (Rate alarm lower limit)
39
0
0
0
0
0
0
0
0
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
b15 b14 b13 b12 b11 b10 b9
b8
b7
b6
b5
b0
b1
b2
b3
b4
(1)
(2)
0
0
0
0
0
0
0
0
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
b15 b14 b13 b12 b11 b10 b9
b8
b7
b6
b5
b0
b1
b2
b3
b4
(1)
(2)
Summary of Contents for MELSEC iQ-F
Page 1: ...MELSEC iQ F FX5 User s Manual Analog Control Intelligent function module ...
Page 2: ......
Page 9: ...7 MEMO ...
Page 181: ......