4 FUNCTIONS
4.10 Shift Function
55
4
Ex.
When the following values are used for multiple input module with the input range of 0 to 5 V
When the shift function is used with the digital clipping function and scaling function, shift-and-add is
performed on the value obtained after digital clipping and scale conversion. Therefore, the range of the digital
operation value is determined as -32768 to +32767.
For a setting example of when the digital clipping function, scaling function, and shift function are used
together, refer to the following.
Item
Setting
‘CH1 Scaling enable/disable setting’ (U\G504)
Enable (0)
‘CH1 Scaling upper limit value’ (Un\G506)
12000
‘CH1 Scaling lower limit value’ (Un\G508)
2000
‘CH1 Conversion shift amount’ (Un\472)
2000
(1)
'CH1 Digital output value' (Un\G400)
Scaling
0 to 32000
↓
2000 to 12000
(2)
Value after scaling
'CH1 Conversion value shift amount' (Un\G472) "+2000"
↓
(3)
'CH1 Digital operation value' (Un\G402)
Voltage input (V)
Digital output value
Value after scaling
Digital operation value
0
0
2000
4000
1
6400
4000
6000
2
12800
6000
8000
3
19200
8000
10000
4
25600
10000
12000
5
32000
12000
14000
32000
14000
12000
2000
4000
0
5
0
(3)
(1)
(2)
Analog input voltage (V)