Mode switching setting
Set a setting value for the mode to be switched.
When a value out of the above is written and 'Operating condition setting request' (Un\G70, b9) is turned
off
→
on
→
off, the mode setting is not performed and only the operating condition is changed.
■
Buffer memory address
The following shows the buffer memory address of this area.
■
Enabling the setting
Turn off
→
on 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■
After the mode is switched
When the mode is switched, this area is cleared to 0 and 'Operating condition setting completed flag' (Un\G69, b9) turns off.
After checking that 'Operating condition setting completed flag’ (Un\G69, b9) is off, turn off 'Operating condition setting
request' (Un\G70, b9).
Rate alarm change rate selection
Select rate alarm change rate. "Rate specification" that sets the rate alarm upper limit value and the rate alarm lower limit
value in units of 0.1% with respect to (the maximum value of the digital output value) - (the minimum value of the digital output
value), and "Digital output value specification" that sets in units of digits for the range of digital output values, can be selected.
When setting to a value other than the above table, it operates with digital output value specification (1).
■
Buffer memory address
The following shows the buffer memory address of this area.
■
Enabling the setting
Turn off
→
on 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■
Default value
Digital output value specification (1) is set.
Switching mode
Setting value
Buffer memory address
296
297
Normal mode
4658H
4144H
Offset/gain setting mode
4144H
4658H
Buffer memory name
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
Mode switching setting
296, 297
Mode switching setting (in FX2N allocation mode function)
126, 127
Setting value
Description
0
Rate specification
1
Digital output value specification
Buffer memory name
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
Rate alarm change rate selection
299
Rate alarm change rate selection (in FX2N allocation mode
function)
130
Summary of Contents for MELSEC iQ-F
Page 1: ...MELSEC iQ F FX5 User s Manual Analog Control Intelligent function module ...
Page 2: ......
Page 9: ...7 MEMO ...
Page 181: ......