Appendix 4 Buffer Memory Areas
CH1 Process alarm lower upper limit value
Set a lower upper limit value of the alert output function (Process alarm).
For details on the alert output function, refer to the following.
■
Buffer memory address
The following shows the buffer memory address of this area.
■
Setting range
The possible setting range is from -32768 to +32767.
■
Enabling the setting
Turn off
→
on
→
off 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■
Default value
The default value is set to 0.
CH1 Process alarm lower lower limit value
Set a lower lower limit value of the alert output function (Process alarm).
For details on the alert output function, refer to the following.
■
Buffer memory address
The following shows the buffer memory address of this area.
■
Setting range
The possible setting range is from -32768 to +32767.
■
Enabling the setting
Turn off
→
on
→
off 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■
Default value
The default value is set to 0.
• When using the process alarm, configure the 4-step settings for the process alarm upper upper limit value,
upper lower limit value, lower upper limit value, and lower lower limit value.
• A channel where the set values do not satisfy the condition "Upper upper limit value
≥
Upper lower limit
value
≥
Lower upper limit value
≥
Lower lower limit value" causes a process alarm upper lower limit value
setting range error (error code: 1B
H).
• When setting the input type to “Current” and “Voltage”, and when the digital clipping function, scaling
function, and shift function are used, the digital operation value to which digital clipping, scale conversion,
and shift-and-add are performed is the detection target for outputting an alert.
• When setting the input type to "resistance temperature detector" or "thermocouple", and the scaling function
and shift function are used, the digital operation value to which scale conversion, and shift-and-add are
performed is the target of outputting an alert (process alarm).
Buffer memory name
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH
Process alarm lower upper limit value
518
718
918
1118
1318
1518
1718
1918
CH
Process alarm lower upper limit value (in FX2N
allocation mode function)
1201
1202
1203
1204
1205
1206
1207
1208
Buffer memory name
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH
Process alarm lower lower limit value
520
720
920
1120
1320
1520
1720
1920
CH
Process alarm lower lower limit value (In FX2N allocation
mode function)
71
72
73
74
75
76
77
78