164
APPX
Appendix 4 Buffer Memory Areas
CH1 Logging cycle unit setting
Set a cycle unit for storing the logging data.
For details on the logging function, refer to the following.
• Setting a value other than the above causes a logging cycle setting value range error (error code: 1D1
H). Logging cannot
be performed.
• If the set logging cycle is below the update cycle of data to be logged, a logging cycle setting disable error (error code:
1D2
H) occurs. Logging cannot be performed.
■
Buffer memory address
The following shows the buffer memory address of this area.
■
Enabling the setting
Turn off
→
on
→
off 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■
Default value
The default value is ms (1).
CH1 Logging points after trigger
Set a number of data points collected for the time period from the occurrence of a hold trigger to the logging stop.
For details on the logging function, refer to the following.
■
Buffer memory address
The following shows the buffer memory address of this area.
■
Setting range
The possible setting range is from 1 to 10000.
Setting a value other than the above causes a post-trigger logging points setting range error (error code: 1D4
H). Logging
cannot be performed.
When 'CH1 Logging enable/disable setting' (Un\G535) is set to Disable (1), the setting for 'CH1 Post-trigger logging points'
(Un\G539) is ignored.
■
Enabling the setting
Turn off
→
on
→
off 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■
Default value
The default value is set to 5000.
Setting value
Setting content
1
ms
2
s
Buffer memory name
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH
Logging cycle unit setting
538
738
938
1138
1338
1538
1738
1938
CH
Logging cycle unit setting (In FX2N allocation mode
function)
9191
9192
9193
9194
9195
9196
9197
9198
Buffer memory name
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH
Post-trigger logging points
539
739
939
1139
1339
1539
1739
1939
CH
Post-trigger logging points (In FX2N allocation mode
function)
9201
9202
9203
9204
9205
9206
9207
9208
Summary of Contents for MELSEC iQ-F