688
14 DIVIDED DATA READ/WRITE FROM/TO BFM INSTRUCTION
14.2 Divided BFM write
■
Related devices
Precautions
• Do not stop the instruction while it is being executed. If driving is stopped, the buffer memory write processing is
suspended, but the data that is already written is stored in (m2) onwards.
• When indexing is executed, the contents of index registers at the beginning of execution are used. Even if the contents of
index registers are changed after the instruction, such changes do not affect the process of the instruction.
• Do not update (change) the contents of (n1) points starting from (s2) while this instruction is executed. If the contents are
updated, the intended data may not be written to the buffer memory areas.
• This instruction cannot be used in FX5 series intelligent function modules.
• This instruction cannot be used while a interrupt routine program is being executed.
Operation error
Device
Name
Description
SM8029
Instruction execution complete
Turns ON when an instruction is finished normally.
SM8328
Instruction non-execution
Turns ON when the RBFM instruction or WBFM instruction in another step is executed for
the same module number.
SM8329
Instruction execution abnormal end
Turns ON when an instruction is finished abnormally.
Error code
(SD0/SD8067)
Description
2441
Communication procedure with module is not completed correctly when this instruction is executed.
2801
Module with the module number specified by (U/H) does not exist or the specified module is not an FX series module.
2823
The number of transfer points specified by (n1) and the buffer memory number specified by (s1) is beyond the buffer memory range.
2820
The number of transfer points specified by (n1) and the device number specified by (s2) is beyond the specified device range.
3580
Instructions that cannot be used in an interrupt routine program are being used.
Summary of Contents for MELSEC iQ-F FX5 series
Page 1: ...MELSEC iQ F FX5 Series Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 21: ...19 PART 1 PART 1 OVERVIEW Part 1 consists of the following chapter 1 OVERVIEW ...
Page 98: ...96 4 STANDARD FUNCTIONS FUNCTION BLOCKS 4 2 Standard Function Blocks MEMO ...
Page 840: ...838 23 TIME DATA FUNCTIONS 23 4 Division MEMO ...
Page 887: ......