608
7 APPLICATION INSTRUCTION
7.21 Module access instruction
Processing details
■
FROM(P)
• These instructions read (n) words of data from the buffer memory specified by (s) in intelligent function module specified by
(U/H), and store the data to the device specified by (d) and later.
■
DFROM(P)
• These instructions read the (n)
2 words of data from the buffer memory specified by (s) in intelligent function module
specified by (U/H), and store the data to the device specified by (d) and later.
Precautions
• For the nibble of a bit device specified by (d), specify K1 to K4 in the FROM(P) instruction and K1 to K8 in the DFROM(P)
instruction.
• When a number greater than 65535 is specified as the buffer memory specified by (s), use the FROMD(P) instruction or
use U
\G
in the MOV(P) instruction. The following shows the program to transfer the buffer memory #70000 in the
intelligent function module No. 1 to D0.
Operation error
Error code
(SD0/SD8067)
Description
2441
Updating procedure with the unit was not properly completed during the execution of the instruction.
2801
The unit number specified by (U/H) does not exist.
2823
The buffer memory number specified by (s) exceeds the buffer memory area.
The buffer memory number specified by (s) + the number of transfer points specified by (n) exceeds the buffer memory area.
2820
The device number specified by (d) + the number of read data specified by (n) exceeds the corresponding device range.
3056
Timeout occurred while communicating with the connected units during the execution of the instruction.
3060
Signal error is detected while accessing the connected units during the execution of the instruction.
3580
The instruction that is disabled in the interrupt routine program is used.
(s)
(d)
Buffer memory
CPU module
(n) points
(n) words
(s)
(d)
CPU module
(n)
2 points
(n)
2 words
Buffer memory
MOV
U1\G70000
D0
SM400
buffer memory #70000
Module No. 1
Transfer
source
Transfer
destination
Summary of Contents for MELSEC iQ-F FX5 series
Page 1: ...MELSEC iQ F FX5 Series Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 21: ...19 PART 1 PART 1 OVERVIEW Part 1 consists of the following chapter 1 OVERVIEW ...
Page 98: ...96 4 STANDARD FUNCTIONS FUNCTION BLOCKS 4 2 Standard Function Blocks MEMO ...
Page 840: ...838 23 TIME DATA FUNCTIONS 23 4 Division MEMO ...
Page 887: ......