102
5 SEQUENCE INSTRUCTIONS
5.1 Contact Instructions
Pulse NOT operation start, pulse NOT series connection, pulse
NOT parallel connection
LDPI, LDFI, ANDPI, ANDFI, ORPI, ORFI
• LDPI: Rising edge pulse NOT operation start instruction
This instruction becomes conductive (ON) at OFF, ON and the falling edge (ON to OFF) of the bit device specified by (s).
• LDFI: Falling edge pulse NOT operation start instruction
This instruction becomes conductive (ON) at the rising edge (OFF to ON), OFF and ON of the bit device specified by (s).
• ANDPI: Rising edge pulse NOT series connection instruction/ANDFI: Falling edge pulse NOT series connection instruction
This instruction ANDs the bit devices specified by (s) with the operation result so far, and uses the result as the operation
result.
• ORPI: Rising edge pulse NOT parallel connection instruction/ORFI: Falling edge pulse NOT parallel connection instruction
This instruction ORs the bit devices specified by (s) with the operation result so far, and uses the result as the operation result.
Setting data
■
Descriptions, ranges, and data types
■
Applicable devices
*1
T, ST, C cannot be used.
Ladder diagram
Structured text
ENO:=LDPI(EN,s);
ENO:=LDFI(EN,s);
ENO:=ANDPI(EN,s);
ENO:=ANDFI(EN,s);
ENO:=ORPI(EN,s);
ENO:=ORFI(EN,s);
Operand
Remarks
Range
Data type
Data type (label)
(s)
Device used as contact
Bit
ANY_BOOL
Operand
Bit
Word
Double word
Indirect
specification
Constant
Others
(DX)
X, Y, M, L,
SM, F, B, SB
U
\G
T, ST,
C, LC
T, ST, C, D,
W, SD, SW, R
U
\G
Z
LC
LZ
K, H
E
$
(s)
(s)
(s)
(s)
(s)
(s)
(s)
LDPI
LDFI
ANDPI
ANDFI
ORPI
ORFI
Summary of Contents for MELSEC iQ-F FX5 series
Page 1: ...MELSEC iQ F FX5 Series Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 21: ...19 PART 1 PART 1 OVERVIEW Part 1 consists of the following chapter 1 OVERVIEW ...
Page 98: ...96 4 STANDARD FUNCTIONS FUNCTION BLOCKS 4 2 Standard Function Blocks MEMO ...
Page 840: ...838 23 TIME DATA FUNCTIONS 23 4 Division MEMO ...
Page 887: ......