Resetting the watchdog timer
WDT(P)
These instructions reset the watchdog timer in a program.
Processing details
• These instructions reset the watchdog timer in a program.
• These instructions are used when the scan time exceeds the value set for the watchdog timer depending on the condition.
If the scan time exceeds the value set for the watchdog timer every scan, change the setting of the watchdog timer in the
parameter setting of the engineering tool.
• Design a program so that t1 from the step 0 to the WDT(P) instruction and t2 from the WDT(P) instruction to the END
(FEND) instruction do not exceed the setting value of the watchdog timer.
• The WDT(P) instruction can be used more than once in one scan. However, note that turning off the output takes some time
if an error occurs.
Precautions
• The time of the watchdog timer can be changed in the [RAS] tab of [CPU Parameter]. The default value is 200 ms.
• By overwriting the contents of SD8000 (watchdog timer time), the watchdog timer detection time can be changed using a
program. When the program shown below is input, the sequence program will be monitored with the new watchdog timer
time.
Operation error
There is no operation error.
Ladder diagram
Structured text
ENO:=WDT(EN);
ENO:=WDTP(EN);
WDT
END (FEND)
t1
t2
Step 0
SD8000
K300
MOV
WDT
SM402
Watchdog timer time: 300 ms
Initial pulse
Refreshes the watchdog timer.
If the WDT instruction is not programmed, the value of
SD8000 is valid during END processing.
Summary of Contents for MELSEC iQ-F FX5 series
Page 1: ...MELSEC iQ F FX5 Series Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 21: ...19 PART 1 PART 1 OVERVIEW Part 1 consists of the following chapter 1 OVERVIEW ...
Page 98: ...96 4 STANDARD FUNCTIONS FUNCTION BLOCKS 4 2 Standard Function Blocks MEMO ...
Page 840: ...838 23 TIME DATA FUNCTIONS 23 4 Division MEMO ...
Page 887: ......