154
6 BASIC INSTRUCTIONS
6.1 Comparison Operation Instructions
Processing details
• These instructions perform a comparison operation on the 16-bit binary data in the device specified by (s1) and the 16-bit
binary data in the device specified by (s2) with the 16-bit binary data in the device specified by comparison source (s3), and
according to the comparison result (below, within zone, above), (d), (d) + 1, or (d) + 2 is turned ON. (s1), (s2), and (s3) are
handled as binary values within the range of above data setting. Large and small comparison is executed algebraically.
• Large and small comparison is executed algebraically.
Precautions
• Set (s1) to a value less than (s2).
• Three devices are occupied from the device specified in (d). Make sure that these devices are not used in other controls.
Operation error
• With sign…
-10 (FFF6H) < 2 (0002H) < 10 (000AH)
• Without sign…
0 (0000H) < 32767 (7FFFH) < 40000 (9C40H)
Error code
(SD0/SD8067)
Description
2820
The range of the 3 points of data starting from the device specified by (d) exceeds said device.
ZCP
(d)
(s1)
(s2)
(s3)
(d)+1
(d)+2
(d)
Turns ON in the case of (s1)>(s3).
Turns ON in the case of (s3)>(s2).
Turns ON in the case of (s1)
≤
(s3)
≤
(s2).
Command input
Even if the command input turns OFF and the ZCP instruction is not executed, (d) to (d)+2 latches the status
just before the command input turns from ON to OFF.
Summary of Contents for MELSEC iQ-F FX5 series
Page 1: ...MELSEC iQ F FX5 Series Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 21: ...19 PART 1 PART 1 OVERVIEW Part 1 consists of the following chapter 1 OVERVIEW ...
Page 98: ...96 4 STANDARD FUNCTIONS FUNCTION BLOCKS 4 2 Standard Function Blocks MEMO ...
Page 840: ...838 23 TIME DATA FUNCTIONS 23 4 Division MEMO ...
Page 887: ......