116
5 SEQUENCE INSTRUCTIONS
5.3 Output Instructions
Setting annunciator
SET F
This instruction turns ON the specified annunciator.
Setting data
■
Descriptions, ranges, and data types
■
Applicable devices
*1
Only F can be used.
Processing details
• This instruction turns ON the annunciator specified by (d) when the execution command turns ON.
• Operation is as follows when annunciator (F) is turned ON.
• When the content of SD63 is 16 (16 annunciators are already ON), the annunciator number that turns ON is not stored in
SD64 to SD79 even if a new annunciator turns ON.
Operation error
There is no operation error.
Ladder diagram
Structured text
ENO:=SET(EN,d);
Operand
Remarks
Range
Data type
Data type (label)
(d)
Annunciator number (F number) that is set
Bit
ANY_BOOL
Operand
Bit
Word
Double word
Indirect
specification
Constant
Others
X, Y, M, L,
SM, F, B, SB
U
\G
T, ST,
C, LC
T, ST, C, D,
W, SD, SW, R
U
\G
Z
LC
LZ
K, H
E
$
(d)
• The annunciator number (F number) that turns ON is stored in special registers (SD64 to SD79).
• The content of SD63 is incremented by 1.
(d)
SD63
SD64
SD65
SD66
SD78
SD79
SD63
SD64
SD65
SD66
SD78
SD79
16
233
90
700
145
1027
16
233
90
700
145
1027
Does not change.
F30 is turned ON.
Summary of Contents for MELSEC iQ-F FX5 series
Page 1: ...MELSEC iQ F FX5 Series Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 21: ...19 PART 1 PART 1 OVERVIEW Part 1 consists of the following chapter 1 OVERVIEW ...
Page 98: ...96 4 STANDARD FUNCTIONS FUNCTION BLOCKS 4 2 Standard Function Blocks MEMO ...
Page 840: ...838 23 TIME DATA FUNCTIONS 23 4 Division MEMO ...
Page 887: ......