666
11 POSITIONING INSTRUCTION
11.1 Positioning Instruction
DPLSV [For the FX5 Series operand specification]
This instruction outputs variable speed pulses with an assigned rotation direction output.
Setting data
■
Descriptions, ranges, and data types
■
Applicable devices
*1
T, ST, C cannot be used.
Processing details
This instruction outputs variable speed pulses with an assigned rotation direction output.
• For (s), specify the command speed to be output. (The speed must be 200 Kpps or lower in frequency.)
• For (d1), specify the axis number from which pulses are output.
• For (d2), specify the bit device of the abnormal end flag for the DPLSV instruction. (This device does not have the normal
complete status, and only has the abnormal end status ((d2)+1).
For details on the function and error code, refer to
Built-in positioning manual.
Precautions
Two devices are occupied from the device specified in (d2). Make sure that these devices are not used in other controls.
For other precautions, refer to
Built-in positioning manual.
Ladder diagram
Structured text
ENO:=DPLSV(EN,s,d1,d2);
Operand
Description
Range
Data type
Data type (label)
(s)
Command speed
-2147483648 to +2147483647
32-bit signed binary
ANY32
(d1)
Axis number from which pulses are to be output
K1 to 4
16-bit signed binary
ANY_ELEMENTARY
(d2)
Bit device number of the positioning complete flag or
abnormal end flag
Bit
ANY_BOOL
Operand
Bit
Word
Double word
Indirect
specification
Constant
Others
X, Y, M, L,
SM, F, B, SB
U
\G
T, ST,
C, LC
T, ST, C, D,
W, SD, SW, R
U
\G
Z
LC
LZ
K, H
E
$
(s)
(d1)
(d2)
(s)
(d1)
(d2)
Summary of Contents for MELSEC iQ-F FX5 series
Page 1: ...MELSEC iQ F FX5 Series Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 21: ...19 PART 1 PART 1 OVERVIEW Part 1 consists of the following chapter 1 OVERVIEW ...
Page 98: ...96 4 STANDARD FUNCTIONS FUNCTION BLOCKS 4 2 Standard Function Blocks MEMO ...
Page 840: ...838 23 TIME DATA FUNCTIONS 23 4 Division MEMO ...
Page 887: ......