474
7 APPLICATION INSTRUCTION
7.10 Data control instruction
Upper and lower limit control of 32-bit binary data
DLIMIT(P)(_U)
These instructions control the output value to be stored in the device specified by (d) by checking the input value (32-bit binary
data) in the device specified by (s3) with the upper and lower limit values specified by (s1) and (s2).
*1
The DLIMIT(_U) instructions are not supported by the ST language. Use LIMIT of the standard function.
Setting data
■
Descriptions, ranges, and data types
■
Applicable devices
Processing details
• These instructions control the output value to be stored in the device specified by (d) by checking the input value (32-bit
binary data) in the device specified by (s3) with the upper and lower limit values specified by (s1) and (s2). The output value
is controlled as follows.
• To control the input value only with the upper limit, set the minimum value within the setting range in (s1).
• To control the input value only with the lower limit, set the maximum value within the setting range in (s2).
Ladder diagram
Structured text
ENO:=DLIMITP(EN,s1,s2,s3,d);
ENO:=DLIMITP_U(EN,s1,s2,s3,d);
Operand
Description
Range
Data type
Data type (label)
(s1)
DLIMIT(P)
Lower limit value (minimum output value)
-2147483648 to +2147483647
32-bit signed binary
ANY32
DLIMIT(P)_U
0 to 4294967295
32-bit unsigned binary
(s2)
DLIMIT(P)
Upper limit value (maximum output value)
-2147483648 to +2147483647
32-bit signed binary
ANY32
DLIMIT(P)_U
0 to 4294967295
32-bit unsigned binary
(s3)
DLIMIT(P)
Input value controlled by the upper and lower
limit values
-2147483648 to +2147483647
32-bit signed binary
ANY32
DLIMIT(P)_U
0 to 4294967295
32-bit unsigned binary
(d)
DLIMIT(P)
Head device number storing the output value
controlled by the upper and lower limit values
32-bit signed binary
ANY32
DLIMIT(P)_U
32-bit unsigned binary
Operand
Bit
Word
Double word
Indirect
specification
Constant
Others
X, Y, M, L,
SM, F, B, SB
U
\G
T, ST,
C, LC
T, ST, C, D,
W, SD, SW, R
U
\G
Z
LC
LZ
K, H
E
$
(s1)
(s2)
(s3)
(d)
Condition
Output value
Lower limit value ((s1), (s1)+1) > Input value ((s3), (s3)+1)
Lower limit value ((s1), (s1)+1)
Upper limit value ((s2), (s2)+1) < Input value ((s3), (s3)+1)
Upper limit value ((s2), (s2)+1)
Lower limit value ((s1), (s1)+1)
Input value ((s3), (s3)+1)
Upper limit value ((s2), (s2)+1)
Input value ((s3), (s3)+1)
(s1)
(s2)
(s3)
(d)
0
Output value (d+1, d)
Input value (s3+1, s3)
Lower limit value (s1+1, s1)
Upper limit value (s2+1, s2)
Summary of Contents for MELSEC iQ-F FX5 series
Page 1: ...MELSEC iQ F FX5 Series Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 21: ...19 PART 1 PART 1 OVERVIEW Part 1 consists of the following chapter 1 OVERVIEW ...
Page 98: ...96 4 STANDARD FUNCTIONS FUNCTION BLOCKS 4 2 Standard Function Blocks MEMO ...
Page 840: ...838 23 TIME DATA FUNCTIONS 23 4 Division MEMO ...
Page 887: ......