290
6 BASIC INSTRUCTIONS
6.5 Data Conversion Instructions
Connecting the specified number of bits
NUNI(P)
These instructions link each bit of the data in the device numbers specified by (s1) onwards into bit units specified by (s2), and
store the connected data in the device number specified by (d) onwards.
Setting data
■
Descriptions, ranges, and data types
■
Applicable devices
Ladder diagram
Structured text
ENO:=NUNI(EN,s1,s2,d);
ENO:=NUNIP(EN,s1,s2,d);
Operand
Description
Range
Data type
Data type (label)
(s1)
Head device for storing the data to be linked
16-bit signed binary
ANY16
(d)
Head device for storing the linked data
16-bit signed binary
ANY16
(s2)
Head device for storing the link unit size
16-bit signed binary
ANY16
Operand
Bit
Word
Double word
Indirect
specification
Constant
Others
X, Y, M, L,
SM, F, B, SB
U
\G
T, ST,
C, LC
T, ST, C, D,
W, SD, SW, R
U
\G
Z
LC
LZ
K, H
E
$
(s1)
(d)
(s2)
(s1)
(d)
(s2)