188
6 BASIC INSTRUCTIONS
6.2 Arithmetic Operation Instructions
DDIV(P)(_U)
These instructions divide the 32-bit binary data in the device specified by (s1) by the 32-bit binary data in the device specified
by (s2), and store the result in the device specified by (d).
Setting data
■
Descriptions, ranges, and data types
■
Applicable devices
Processing details
• These instructions divide the 32-bit binary data in the device specified by (s1) by the 32-bit binary data in the device
specified by (s2), and store the division result in the device specified by (d).
■
Related flag
Precautions
■
Operation result
• The most significant bit of the quotient and remainder indicates the sign (positive: 0, negative: 1), respectively.
• The quotient is negative when either (s1) or (s2) is negative. The remainder is negative when the (s1) is negative.
■
Device specified by (d)
• The remainder is not obtained when a bit device is specified with nibble specification.
Ladder diagram
Structured text
ENO:=DDIV(EN,s1,s2,d);
ENO:=DDIVP(EN,s1,s2,d);
ENO:=DDIV_U(EN,s1,s2,d);
ENO:=DDIVP_U(EN,s1,s2,d);
Operand
Description
Range
Data type
Data type (label)
(s1)
DDIV(P)
Dividend data or the head device where the
data to be divided by another is stored
-2147483648 to +2147483647
32-bit signed binary
ANY32_S
DDIV(P)_U
0 to 4294967295
32-bit unsigned binary
ANY32_U
(s2)
DDIV(P)
Divisor data or the head device where the data
by which another is to be divided is stored
-2147483648 to +2147483647
32-bit signed binary
ANY32_S
DDIV(P)_U
0 to 4294967295
32-bit unsigned binary
ANY32_U
(d)
DDIV(P)
Head device for storing the operation result
64-bit signed binary
ANY32_S_ARRAY
(Number of elements:
2)
DDIV(P)_U
64-bit unsigned binary
ANY32_U_ARRAY
(Number of elements:
2)
Operand
Bit
Word
Double word
Indirect
specification
Constant
Others
X, Y, M, L,
SM, F, B, SB
U
\G
T, ST,
C, LC
T, ST, C, D,
W, SD, SW, R
U
\G
Z
LC
LZ
K, H
E
$
(s1)
(s2)
(d)
Device
Name
Description
SM700
Carry
When the operation result of the signed operation exceeds 32767, the carry flag is turned ON.
SM8304
Zero
When the operation result is 0, the zero flag is turned ON.
SM8306
Carry
When the operation result of the signed operation exceeds 32767, the carry flag is turned ON.
(s1)
(s2)
(d)
567890 (BIN)
123456 (BIN)
4 (BIN)
÷
(d)
(d)+1
b0
···
···
b31
b16 b15
(s2)
(s2)+1
b0
···
···
b31
b16 b15
(s1)
(s1)+1
b0
···
···
b31
b16 b15
74066 (BIN)
(d)+2
(d)+3
b0
···
···
b31
b16 b15
Summary of Contents for MELSEC iQ-F FX5 series
Page 1: ...MELSEC iQ F FX5 Series Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 21: ...19 PART 1 PART 1 OVERVIEW Part 1 consists of the following chapter 1 OVERVIEW ...
Page 98: ...96 4 STANDARD FUNCTIONS FUNCTION BLOCKS 4 2 Standard Function Blocks MEMO ...
Page 840: ...838 23 TIME DATA FUNCTIONS 23 4 Division MEMO ...
Page 887: ......