136
5 SEQUENCE INSTRUCTIONS
5.4 Shift Instructions
Shifting n-word data to the left by n word(s)
WSFL(P)
This instruction shifts (n1) words of data to the left by (n2) word(s) from the device specified by (d).
Setting data
■
Descriptions, ranges, and data types
*1
Set so that n2
n1.
■
Applicable devices
Processing details
• This instruction shifts (n1) words of data to the left by (n2) word(s) from the device specified by (d). After the shift, (n2)
points from (s) are set into (n2) points from (d).
• This instruction sets the specified value for (n2) points of devices from (d) + (n1-n2) after the shift when K is specified for
(s).
• When the value specified for (n1) or (n2) is 0, the processing is not performed.
Operation error
Ladder diagram
Structured text
ENO:=WSFL(EN,s,n1,n2,d);
ENO:=WSFLP(EN,s,n1,n2,d);
Operand
Remarks
Range
Data type
Data type (label)
(s)
Head device number stored to the shift data after the shift
Word
ANY16
(d)
Head device number to be shifted
Word
ANY16
(n1)
Data length of shift data
0 to 65535
16-bit unsigned binary
ANY16_U
(n2)
Number of shifts
0 to 65535
16-bit unsigned binary
ANY16_U
Operand
Bit
Word
Double word
Indirect
specification
Constant
Others
X, Y, M, L,
SM, F, B, SB
U
\G
T, ST,
C, LC
T, ST, C, D,
W, SD, SW, R
U
\G
Z
LC
LZ
K, H
E
$
(s)
(d)
(n1)
(n2)
Error code
(SD0/SD8067)
Remarks
2820
The (n2) points of data starting from the device specified by (s) exceed in the corresponding device.
The (n1) points of data starting from the device specified by (d) exceed in the corresponding device.
2821
The transfer source data (s) overlaps with shift device (d).
3405
A constant other than K0 or K1 is specified when the constant (s) is specified.
The values specified in (n1) and (n2) are such that (n1)<(n2).
(s)
(d)
(n1)
(n2)
10H
0H
7FFH
3AH
1FH
30H
0H
FFH
1FFH
0H
0H
0H
0H
3AH
1FH
30H
0H
FFH
(n1)
(n2)
(d)+8
(d)+7
(d)+6
(d)+5
(d)+4
(d)+3
(d)+2
(d)+1
(d)
(d)+8
(d)+7
(d)+6
(d)+5
(d)+4
(s)+3
(s)+2
(s)+1
(s)
Summary of Contents for MELSEC iQ-F FX5 series
Page 1: ...MELSEC iQ F FX5 Series Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 21: ...19 PART 1 PART 1 OVERVIEW Part 1 consists of the following chapter 1 OVERVIEW ...
Page 98: ...96 4 STANDARD FUNCTIONS FUNCTION BLOCKS 4 2 Standard Function Blocks MEMO ...
Page 840: ...838 23 TIME DATA FUNCTIONS 23 4 Division MEMO ...
Page 887: ......