602
7 APPLICATION INSTRUCTION
7.20 Timing check instruction
• When the command input is set to ON, the operation is started. The special relay of the timing clock output destination is
set to ON or OFF by the END instruction. Even if the command input is set to OFF, the operation is not stopped. In the
STOP mode, the operation is stopped. When the power to the CPU module is turned OFF, the operation is stopped.
• When (n1) and (n2) are set to "0", the status is as shown below:
• The table below shows the related devices.
Precautions
• The DUTY instruction can be used up to 5 times (points). It is not permitted, however, to use the same timing clock output
destination device for two or more DUTY instructions.
Operation error
Status of (n1) and (n2)
ON/OFF status of (d)
(n1)=0, (n2)
0
(d)= Fixed to OFF
(n1)>0, (n2)=0
(d)= Fixed to ON
Special relay
Name
Description
SM420(SM8330)
Timing clock output 1
Timing clock output in the DUTY instruction
SM421(SM8331)
Timing clock output 2
SM422(SM8332)
Timing clock output 3
SM423(SM8333)
Timing clock output 4
SM424(SM8334)
Timing clock output 5
Special register
Name
Description
SD8330
Counted number of scans for timing clock output 1
Counted number of scans for timing clock output 1 in the DUTY
instruction
SD8331
Counted number of scans for timing clock output 2
Counted number of scans for timing clock output 2 in the DUTY
instruction
SD8332
Counted number of scans for timing clock output 3
Counted number of scans for timing clock output 3 in the DUTY
instruction
SD8333
Counted number of scans for timing clock output 4
Counted number of scans for timing clock output 4 in the DUTY
instruction
SD8334
Counted number of scans for timing clock output 5
Counted number of scans for timing clock output 5 in the DUTY
instruction
Error code
(SD0/SD8067)
Description
2820
The device specified by (d) is out of the range from SM420 to SM424 (SM8330 to SM8334).
Summary of Contents for MELSEC iQ-F FX5 series
Page 1: ...MELSEC iQ F FX5 Series Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 21: ...19 PART 1 PART 1 OVERVIEW Part 1 consists of the following chapter 1 OVERVIEW ...
Page 98: ...96 4 STANDARD FUNCTIONS FUNCTION BLOCKS 4 2 Standard Function Blocks MEMO ...
Page 840: ...838 23 TIME DATA FUNCTIONS 23 4 Division MEMO ...
Page 887: ......