Service
- 197 -
‘19 • HM-T-340
Alarm list
Outdoor unit alarm
Alarm
No.
Alarm text on the
display
Description
May be due to
E5
Com. flt from the heat
pump
Communication between the control
board and the communication board is
interrupted. There must be 22 Volt direct
current (DC) at the switch CNW2 on the
control board (PCB1).
- Any circuit breakers for FDCW off
- Incorrect cable routing
E35 High HWX temp
Temperature deviation on the heat exchanger
sensor (Tho-R1/R2) fi ve times within
60 minutes or for 60 minutes continuously.
- Sensor does not work
(see section "Disturbances in comfort")
- Insuffi cient air circulation or blocked
heat exchanger
- Defective control board in FDCW
- Too much refrigerant
E36 Hot gas alarm
Temperature deviation on the hot gas
sensor (Tho-D) twice within 60 minutes
or for 60 minutes continuously.
- Sensor does not work
(see section "Ambient temperature sensor")
- Insuffi cient air circulation or heat exchanger
- Blocked
- If the fault persists during cooling,
there may be an insuffi cient amount of refrigerant.
- Defective control board in FDCW
E37 Sensor fault from heat
pump
Sensor fault, heat exchanger in
FDCW(Tho-R).
- Open circuit or short circuit on sensor input
- Sensor does not work
(see section "Disturbances in comfort")
- Defective control board in FDCW
E38 Sensor fault from heat
pump
Sensor fault, outdoor temperature sensor
in FDCW (Tho-A).
- Open circuit or short circuit on sensor input
- Sensor does not work
(see section "Disturbances in comfort")
- Defective control board in FDCW
E39 Sensor fault from heat
pump
Sensor fault, hot gas in FDCW (Tho-D).
- Open circuit or short circuit on sensor input
- Sensor does not work
(see section "Disturbances in comfort")
- Defective control board in FDCW
E40 High pressure alarm
The high pressure switch (63H1) deployed
5 times within 60 minutes.
2HP model: BP4 has been above 4.15MPa
5 times within 60 minutes.
- Insuffi cient air circulation or blocked
heat exchanger
- Open circuit or short circuit on input
for high pressure switch (63H1)
- Defective high pressure switch
- Expansion valve not correctly connected
- Service valve closed
- Defective control board in FDCW
- Low or no fl ow during heating operation
- Defective circulation pump
- Defective fuse, F(4A)
E41 Inv. err.
When IPM (Intelligent power module)
displays FO-signal (Fault Output) fi ve
times during a 60-minute period.
Can occur when 15V power source to
the inverter PCB is unstable.
E42 Inv. err.
Voltage from the inverter outside the
parameters four times within 30 minutes.
- Incoming power source interference
- Service valve closed
- Insuffi cient amount of refrigerant
- Compressor fault
- Defective circuit board for inverter in FDCW
Summary of Contents for FDCW100VNX-A
Page 7: ... 5 Technical data 19 HM T 340 Technical data ...
Page 36: ... 34 Technical data 19 HM T 340 Dimensions FDCW71VNX A Meaning of symbol ...
Page 38: ... 36 Technical data 19 HM T 340 FDCW140VNX A Meaning of symbol Dimensions ...
Page 41: ... 39 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 42: ... 40 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 43: ... 41 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 44: ... 42 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 45: ... 43 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 46: ... 44 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 47: ... 45 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 48: ... 46 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 49: ... 47 Technical data 19 HM T 340 Electrical circuit diagram Split box HSB60 W ...
Page 50: ... 48 Technical data 19 HM T 340 HSB100 Electrical circuit diagram ...
Page 51: ... 49 Technical data 19 HM T 340 HSB140 Electrical circuit diagram ...
Page 52: ... 50 Technical data 19 HM T 340 Electrical circuit diagram Outdoor units FDCW60VNX A ...
Page 57: ... 55 Technical data 19 HM T 340 Electrical circuit diagram POWER SOURCE RC HY20 W sheet 3 ...
Page 58: ... 56 Technical data 19 HM T 340 Electrical circuit diagram RC HY20 W sheet 4 ...
Page 61: ... 59 Technical data 19 HM T 340 Electrical circuit diagram POWER SOURCE RC HY40 W sheet 3 ...
Page 62: ... 60 Technical data 19 HM T 340 Electrical circuit diagram RC HY40 W sheet 4 ...
Page 64: ... 62 Technical data 19 HM T 340 Electrical circuit diagram RC HY40 W sheet 6 ...
Page 65: ...Installation 19 HM T 340 Installation 63 ...
Page 133: ...Control 19 HM T 340 Control 131 ...
Page 170: ... 168 Service 19 HM T 340 Service ...
Page 263: ... 258 Service 19 HM T 340 Outdoor unit FDCW60VNX FDCW71VNX Component replacement ...
Page 264: ...Service 259 19 HM T 340 FDCW100VNX FDCW140VNX LEK LEK Component replacement ...
Page 290: ... 285 Components 19 HM T 340 Components ...
Page 300: ... 295 Components 19 HM T 340 PT300 Component positions ...
Page 301: ... 296 Components 19 HM T 340 Component positions PT300 PT300 A mm 1634 B mm 743 C mm 673 ...
Page 302: ... 297 Components 19 HM T 340 PT500 Component positions ...
Page 303: ... 298 Components 19 HM T 340 PT500 Component positions PT500 A mm 1835 B mm 897 C mm 832 ...
Page 311: ...THo R THo A THo D Outside units FDCW60VNX 306 Components 19 HM T 340 Piping system ...