- 188 -
Service
‘19 • HM-T-340
<
FDCW71, 100, 140VNX
>
a) Protective control
i) When the outdoor air temperature (Tho-A) is 40°C or higher and the outdoor heat exchanger temperature (Tho-R)
exceeds setting value, the compressor speed (frequency) is controlled in order to suppress the rise of high
pressure.
ii) The control value A is updated to an optimum value automatically according to the operating conditions.
Control value A
54-60°C
Outdoor heat exchanger temperature (°C)
A
Reset
Reduce compressor
speed at every 1minute
b) Anomalous stop control
i) If the outdoor heat exchanger temperature (Tho-R) exceeds the setting value, the compressor stops.
ii) When the outdoor heat exchanger temperature anomaly is detected 5 times within 60 minutes, or 60 minutes
continuously including the time of compressor stopping, cooling overload error is displayed and E35 is recorded
in the Error Log and it enters the anomalous stop mode.
51
65
Compressor stop
Compressor operation
Outdoor heat exchanger temperature (°C)
c) Reset of anomalous stop mode
When the outdoor heat exchanger temperature drops to the reset value of 51°C or lower, it becomes possible to restart
from the control.
b) Anomalous stop control
i) If the outdoor heat exchanger temperature (Tho-R) exceeds the setting value, the compressor stop.
ii) Whe n the outdoor heat exchanger temperature anomaly is detected 5times within 60 minutes, or 60 minutes
continuously including the time of compressor stopping, coolinf overload error is displayed and E35 is recorded
in the Error Log and it enters the anomalous stop mode.
Compressor operation
Compressor stop
A zone P1 P3
B zone P1 P3
Outdoor heat exchanger temperature(
℃
)
c) Reset of anomalous stop mode
When the outdoor heat exchanger temperature drops to the reset value P3
℃
or lower, it becomes possible to restart
from the control.
Operation control function by the outdoor unit control
Summary of Contents for FDCW100VNX-A
Page 7: ... 5 Technical data 19 HM T 340 Technical data ...
Page 36: ... 34 Technical data 19 HM T 340 Dimensions FDCW71VNX A Meaning of symbol ...
Page 38: ... 36 Technical data 19 HM T 340 FDCW140VNX A Meaning of symbol Dimensions ...
Page 41: ... 39 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 42: ... 40 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 43: ... 41 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 44: ... 42 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 45: ... 43 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 46: ... 44 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 47: ... 45 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 48: ... 46 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 49: ... 47 Technical data 19 HM T 340 Electrical circuit diagram Split box HSB60 W ...
Page 50: ... 48 Technical data 19 HM T 340 HSB100 Electrical circuit diagram ...
Page 51: ... 49 Technical data 19 HM T 340 HSB140 Electrical circuit diagram ...
Page 52: ... 50 Technical data 19 HM T 340 Electrical circuit diagram Outdoor units FDCW60VNX A ...
Page 57: ... 55 Technical data 19 HM T 340 Electrical circuit diagram POWER SOURCE RC HY20 W sheet 3 ...
Page 58: ... 56 Technical data 19 HM T 340 Electrical circuit diagram RC HY20 W sheet 4 ...
Page 61: ... 59 Technical data 19 HM T 340 Electrical circuit diagram POWER SOURCE RC HY40 W sheet 3 ...
Page 62: ... 60 Technical data 19 HM T 340 Electrical circuit diagram RC HY40 W sheet 4 ...
Page 64: ... 62 Technical data 19 HM T 340 Electrical circuit diagram RC HY40 W sheet 6 ...
Page 65: ...Installation 19 HM T 340 Installation 63 ...
Page 133: ...Control 19 HM T 340 Control 131 ...
Page 170: ... 168 Service 19 HM T 340 Service ...
Page 263: ... 258 Service 19 HM T 340 Outdoor unit FDCW60VNX FDCW71VNX Component replacement ...
Page 264: ...Service 259 19 HM T 340 FDCW100VNX FDCW140VNX LEK LEK Component replacement ...
Page 290: ... 285 Components 19 HM T 340 Components ...
Page 300: ... 295 Components 19 HM T 340 PT300 Component positions ...
Page 301: ... 296 Components 19 HM T 340 Component positions PT300 PT300 A mm 1634 B mm 743 C mm 673 ...
Page 302: ... 297 Components 19 HM T 340 PT500 Component positions ...
Page 303: ... 298 Components 19 HM T 340 PT500 Component positions PT500 A mm 1835 B mm 897 C mm 832 ...
Page 311: ...THo R THo A THo D Outside units FDCW60VNX 306 Components 19 HM T 340 Piping system ...