Service
- 189 -
‘19 • HM-T-340
3) Heating high pressure protection
<
FDCW60VNX
>
a) Protective control
If the liquid line temperature of water heat exchanger (BT15=Thi-L) or the condensing saturated temperature (CST),
whichever the higher.
Exceeds the setting value, the compressor speed (frequency) is controlled at every 10 seconds to suppress the rise of
high pressure.
Reset
65
63
Reduce compressor speed by 4 rps
Reduce compressor speed by 8 rps
Tho-R(
℃
)
<
FDCW71, 100, 140VNX
>
a) Protective control
i) If the liquid line temperature of water heat exchanger (BT15=Thi-L) or the condensing saturated temperature
(CST), whichever the higher, exceeds the setting value, the compressor speed (frequency) is controlled to
suppress the rise of high pressure.
ii) Control value A is updated to an optimum value automatically according to the operating conditions.
60-63°C
Reset
Reduce compressor speed at every 10 seconds
Liquid line temperature of water heat exchanger or
condensing satureted temperature (°C)
b) Anomalous stop control
If the liquid line temperature of water heat exchanger (BT15=Thi-L) or the condensing saturated temperature (CST),
whichever the higher, exceeds the setting value for 2 seconds, compressor stops.
The compressor automatically restarts when the temperature gets 47°C or lower.
47
65
Compressor stop
Compressor operation
Liquid line temperature of water heat exchanger or
condensing satureted temperature (°C)
4) Anomaly detection control by the high pressure switch (63H1)
i) If the high pressure rises and activates the high pressure switch (opens at 4.15MPa/close at 3.15MPa), the
compressor stops.
ii) Under any of following conditions, HP alarm is displayed and E40 is recorded in the Error Log, and it enters the
anomalous stop mode.
①
When high pressure exceeds the setting value and the compressor is stopped by 63H1 5 times. within 60 minutes.
②
When 63H1 has been in the open state for 60 minutes continuously including the time of compressor stopping.
5) Low pressure control
a) Protective control
If the value detected by the low pressure sensor (LTP) exceeds the setting value, the compressor speed (frequency) is
controlled to restrain the drop of pressure.
0.150
0.189
Reduce compressor speed at every 30 seconds
Reset
Low pressure (MPa)
Retention
Operation control function by the outdoor unit control
Summary of Contents for FDCW100VNX-A
Page 7: ... 5 Technical data 19 HM T 340 Technical data ...
Page 36: ... 34 Technical data 19 HM T 340 Dimensions FDCW71VNX A Meaning of symbol ...
Page 38: ... 36 Technical data 19 HM T 340 FDCW140VNX A Meaning of symbol Dimensions ...
Page 41: ... 39 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 42: ... 40 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 43: ... 41 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 44: ... 42 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 45: ... 43 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 46: ... 44 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 47: ... 45 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 48: ... 46 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 49: ... 47 Technical data 19 HM T 340 Electrical circuit diagram Split box HSB60 W ...
Page 50: ... 48 Technical data 19 HM T 340 HSB100 Electrical circuit diagram ...
Page 51: ... 49 Technical data 19 HM T 340 HSB140 Electrical circuit diagram ...
Page 52: ... 50 Technical data 19 HM T 340 Electrical circuit diagram Outdoor units FDCW60VNX A ...
Page 57: ... 55 Technical data 19 HM T 340 Electrical circuit diagram POWER SOURCE RC HY20 W sheet 3 ...
Page 58: ... 56 Technical data 19 HM T 340 Electrical circuit diagram RC HY20 W sheet 4 ...
Page 61: ... 59 Technical data 19 HM T 340 Electrical circuit diagram POWER SOURCE RC HY40 W sheet 3 ...
Page 62: ... 60 Technical data 19 HM T 340 Electrical circuit diagram RC HY40 W sheet 4 ...
Page 64: ... 62 Technical data 19 HM T 340 Electrical circuit diagram RC HY40 W sheet 6 ...
Page 65: ...Installation 19 HM T 340 Installation 63 ...
Page 133: ...Control 19 HM T 340 Control 131 ...
Page 170: ... 168 Service 19 HM T 340 Service ...
Page 263: ... 258 Service 19 HM T 340 Outdoor unit FDCW60VNX FDCW71VNX Component replacement ...
Page 264: ...Service 259 19 HM T 340 FDCW100VNX FDCW140VNX LEK LEK Component replacement ...
Page 290: ... 285 Components 19 HM T 340 Components ...
Page 300: ... 295 Components 19 HM T 340 PT300 Component positions ...
Page 301: ... 296 Components 19 HM T 340 Component positions PT300 PT300 A mm 1634 B mm 743 C mm 673 ...
Page 302: ... 297 Components 19 HM T 340 PT500 Component positions ...
Page 303: ... 298 Components 19 HM T 340 PT500 Component positions PT500 A mm 1835 B mm 897 C mm 832 ...
Page 311: ...THo R THo A THo D Outside units FDCW60VNX 306 Components 19 HM T 340 Piping system ...