Installation
'19 • HM-T-340
Indoor unit installation
AUX inputs
Up to 6 other external inputs are available on RC-HY40
-W
.
AUX1 through 3 correspond to the port 9/10, 11/12, 13/14
respectively on X6 terminal on AA3 board. AUX4 through 6
correspond to the port 1, 2 and 3 on X2 terminal on RC-HY40.
Port 4 on X2 terminal is GND and is common to AUX4
through 6. Connect a sensor or switch between AUX and GND
with a 2 cores cable with a minimum cross section of 0.5mm
2
.
AUX1
AUX2
AUX3
RC-HY40
-W
AUX4
A
UX5
GND
A
UX6
AA3-X6
X2
Select the appropriate function in menu 5.4.
block heating
activate temp lux
not used
soft in/outputs
5.4
not used
not used
not used
■ Temperature sensor, external supply at additional heat before
reversing valve (BT63)
Temperature sensor BT63 is applied in case additional heater
is placed before 3-way valve (see page 287 for diagram)
The following functions are available. For details, see AUX
inputs for RC-HY20
-W
.
■ Temperature sensor, cooling/heating (BT74)
■ Temperature sensor, external return line (BT71)
■ Temperature sensor, fl ow line cooling (BT64)
■ Contact for external tariff blocking
■ Switch for “SG ready”
■Contact for activation of “temporary lux”
■Contact for activation of “external adjustment”
■Switch for external alarm
■Switch for external blocking
AUX outputs
External output is available on the port NC, NO and C on X7
terminal on AA3 board on RC-HY40
-W
. The relay output
can have a max load of 2A at resistive load.
Following functions are available. Select the function in menu
5.4.
Indication of buzzer alarm
When an alarm occurs, the circuit becomes closed between
the port NO and C. During normal operation, the port NC
and C is closed.
Cooling mode indication / Active cooling mode (4-pipe
cooling)
When the system turns into cooling mode, the circuit
becomes closed between the port NO and C. By using this
signal, it is possible to switch 3-way valve for 4-pipe cooling
or to assemble a display circuit indicating cooling mode. For
details of connecting the 3-way valve, refer to pages 98 and
99.
External pump control (GP10)
External pump (GP10) is used in case additional heater is
placed after 3-way valve that switches heating/hot water
(refer to page 288 for diagram).
Connect the circulation pump using the port NO and C on
X7 terminal on AA3 board as shown below.
C
N
O
N
C
Externt
L
PE
N
N
PE
L
External
AA3-X7
AA3-X7
RC-HY40
-W
Hot water circulation pump control (GP11)
In case the distance between hot water tap and hot water
storage tank is far, the hot water supply line temperature is
likely to drop and it may take time to supply hot water from
the tap. In that case, hot water circulation pump (GP11) is
applied to maintain hot water supply line temperature warm
(refer to pages 86, 87 for diagram).
For details of connecting the pump, refer to External pump
control (GP10).
NOTE
Mark up any junction boxes with warnings for external
voltage.
- 110 -
R
C-HY40-W
#
Summary of Contents for FDCW100VNX-A
Page 7: ... 5 Technical data 19 HM T 340 Technical data ...
Page 36: ... 34 Technical data 19 HM T 340 Dimensions FDCW71VNX A Meaning of symbol ...
Page 38: ... 36 Technical data 19 HM T 340 FDCW140VNX A Meaning of symbol Dimensions ...
Page 41: ... 39 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 42: ... 40 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 43: ... 41 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 44: ... 42 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 45: ... 43 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 46: ... 44 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 47: ... 45 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 48: ... 46 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 49: ... 47 Technical data 19 HM T 340 Electrical circuit diagram Split box HSB60 W ...
Page 50: ... 48 Technical data 19 HM T 340 HSB100 Electrical circuit diagram ...
Page 51: ... 49 Technical data 19 HM T 340 HSB140 Electrical circuit diagram ...
Page 52: ... 50 Technical data 19 HM T 340 Electrical circuit diagram Outdoor units FDCW60VNX A ...
Page 57: ... 55 Technical data 19 HM T 340 Electrical circuit diagram POWER SOURCE RC HY20 W sheet 3 ...
Page 58: ... 56 Technical data 19 HM T 340 Electrical circuit diagram RC HY20 W sheet 4 ...
Page 61: ... 59 Technical data 19 HM T 340 Electrical circuit diagram POWER SOURCE RC HY40 W sheet 3 ...
Page 62: ... 60 Technical data 19 HM T 340 Electrical circuit diagram RC HY40 W sheet 4 ...
Page 64: ... 62 Technical data 19 HM T 340 Electrical circuit diagram RC HY40 W sheet 6 ...
Page 65: ...Installation 19 HM T 340 Installation 63 ...
Page 133: ...Control 19 HM T 340 Control 131 ...
Page 170: ... 168 Service 19 HM T 340 Service ...
Page 263: ... 258 Service 19 HM T 340 Outdoor unit FDCW60VNX FDCW71VNX Component replacement ...
Page 264: ...Service 259 19 HM T 340 FDCW100VNX FDCW140VNX LEK LEK Component replacement ...
Page 290: ... 285 Components 19 HM T 340 Components ...
Page 300: ... 295 Components 19 HM T 340 PT300 Component positions ...
Page 301: ... 296 Components 19 HM T 340 Component positions PT300 PT300 A mm 1634 B mm 743 C mm 673 ...
Page 302: ... 297 Components 19 HM T 340 PT500 Component positions ...
Page 303: ... 298 Components 19 HM T 340 PT500 Component positions PT500 A mm 1835 B mm 897 C mm 832 ...
Page 311: ...THo R THo A THo D Outside units FDCW60VNX 306 Components 19 HM T 340 Piping system ...