Control
‘19 • HM-T-340
Menu 1.9.4 - room sensor settings
factor system
room sensor settings
1.9.4
heating factor system
1
control room sensor syst 2
control room sensor syst 3
cooling factor system
1
control room sensor syst 1
control room sensor syst 4
* If there is one climate system, display shows "control room sensor
system 1" only.
heating
Setting range: 0.0 – 6.0
Factory setting heating: 2.0
cooling (accessory required)
Setting range: 0.0 – 6.0
Factory setting cooling: 1.0
Room sensors to control the room temperature can be activated
here.
CAUTION
A slow heat-releasing heating system, such as for example,
underfloor heating, may not be suitable for control using
the heat pump's room sensor.
Here you can set a factor (a numerical value) that determines
how much an over or sub normal temperature (the diff erence
between the desired and actual room temperature) in the room
is to affect the supply temperature to the climate system. A
higher value gives a greater and faster change of the heating
curve's set off set.
NOTE
Too high a set value for "factor system" can (depending on
your climate system) produce an unstable room
temperature.
If several climate systems are installed the above settings can
be made for the relevant systems.
Menu 1.9.3 - min. flow line temp.
min. flow line temp. heating
1.9.3.1
climate system 1
climate system 2
climate system 3
climate system 4
°C
°C
°C
°C
20
20
20
20
min. flow line temp. cooling
1.9.3.2
climate system 1
climate system 2
climate system 3
climate system 4
°C
°C
°C
°C
18
18
18
18
* If there is one climate system, display shows "climate system 1" only.
heating
Setting range: 5 – 70 °C
Default value: 20 °C
cooling (heat pump with cooling function required)
Depending on which cooling function (2-pipe /4-pipe-system)
is used, the lower limit of the setting range can vary from 7 to
18 °C.
Setting range: 7 – 30 °C
Factory setting: 18 °C
In menu 1.9.3 you select heating or cooling, in the next menu (min.
supply temp. heating/cooling) set the minimum temperature on the
supply temperature to the climate system. This means that RC-
HY20/40
-W
never calculates a temperature lower than that set
here.
If there is more than one climate system the setting can be
made separately for each system.
TIP
The value can be increased if you have, for example, a cellar
that you always want to heat, even in summer.
You may also need to increase the value in "stop heating"
menu 4.9.2 "auto mode setting".
Control
- 143 -
#
Summary of Contents for FDCW100VNX-A
Page 7: ... 5 Technical data 19 HM T 340 Technical data ...
Page 36: ... 34 Technical data 19 HM T 340 Dimensions FDCW71VNX A Meaning of symbol ...
Page 38: ... 36 Technical data 19 HM T 340 FDCW140VNX A Meaning of symbol Dimensions ...
Page 41: ... 39 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 42: ... 40 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 43: ... 41 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 44: ... 42 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 45: ... 43 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 46: ... 44 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 47: ... 45 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 48: ... 46 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 49: ... 47 Technical data 19 HM T 340 Electrical circuit diagram Split box HSB60 W ...
Page 50: ... 48 Technical data 19 HM T 340 HSB100 Electrical circuit diagram ...
Page 51: ... 49 Technical data 19 HM T 340 HSB140 Electrical circuit diagram ...
Page 52: ... 50 Technical data 19 HM T 340 Electrical circuit diagram Outdoor units FDCW60VNX A ...
Page 57: ... 55 Technical data 19 HM T 340 Electrical circuit diagram POWER SOURCE RC HY20 W sheet 3 ...
Page 58: ... 56 Technical data 19 HM T 340 Electrical circuit diagram RC HY20 W sheet 4 ...
Page 61: ... 59 Technical data 19 HM T 340 Electrical circuit diagram POWER SOURCE RC HY40 W sheet 3 ...
Page 62: ... 60 Technical data 19 HM T 340 Electrical circuit diagram RC HY40 W sheet 4 ...
Page 64: ... 62 Technical data 19 HM T 340 Electrical circuit diagram RC HY40 W sheet 6 ...
Page 65: ...Installation 19 HM T 340 Installation 63 ...
Page 133: ...Control 19 HM T 340 Control 131 ...
Page 170: ... 168 Service 19 HM T 340 Service ...
Page 263: ... 258 Service 19 HM T 340 Outdoor unit FDCW60VNX FDCW71VNX Component replacement ...
Page 264: ...Service 259 19 HM T 340 FDCW100VNX FDCW140VNX LEK LEK Component replacement ...
Page 290: ... 285 Components 19 HM T 340 Components ...
Page 300: ... 295 Components 19 HM T 340 PT300 Component positions ...
Page 301: ... 296 Components 19 HM T 340 Component positions PT300 PT300 A mm 1634 B mm 743 C mm 673 ...
Page 302: ... 297 Components 19 HM T 340 PT500 Component positions ...
Page 303: ... 298 Components 19 HM T 340 PT500 Component positions PT500 A mm 1835 B mm 897 C mm 832 ...
Page 311: ...THo R THo A THo D Outside units FDCW60VNX 306 Components 19 HM T 340 Piping system ...