- 190 -
Service
‘19 • HM-T-340
b) Anomalous stop control
i) When a value detected by the low pressure sensor (LPT) satisfi es any of the following conditions, compressor stops.
①
When the low pressure drops to 0.079MPa or lower for 15 seconds continuously.
ii) Under any of the following conditions, LP alarm is displayed and E49 is recorded in Error Log, and it enters the
anomalous stop mode.
①
When the low pressure drops and the compressor stops under any of above conditions 3 times within 60 minutes.
②
When the low pressure sensor detects 0.079MPa for 5 minutes continuously including the time of compressor stopping
③
However, when the control condition
①
is established during the control of the compressor protection start
Ⅲ
, LP alarm
is displayed and E49 is recorded in Error Log at the fi rst stop of compressor and it enters the anomalous stop mode.
6) Overcurrent protection
<
FDCW60VNX
>
When the inverter primary current (CT current) reaches following value, the compressor speed
is reduced until it gets to the cancellation value.
Operation mode
Current (A)
Cooling
11.5
Heating
13.5
<
FDCW71, 100, 140VNX
>
a) Current safe control I
When the inverter primary current (CT current) reaches following value, the compressor speed
is reduced until it gets to the cancellation value.
Model
Operation Mode
Current (A)
FDCW71VNX
Cooling
15
Heating
16
FDCW100VNX
Cooling
17
Heating
17
FDCW140VNX
Cooling
23
Heating
25
b) Current safe control II
Detecting the outdoor inverter output (secondary side) current, if the current values exceed setting values, the
compressor speed (frequency) is controlled in order to protect the inverter.
B
A
Reduce compressor speed
at every 1minute
Reset
Current (A)
Retention
12
14
16
18
20
22
24
50
40
60 70 80 90 100 110 120 130
Control or reset valve (A)
Compressor speed (frequency) (rps)
(Fig. C) The control value “A” and the reset value vary depending
on the compressor speed.
Reset valve B
Control valve A
Model
Cooling
Heating
Control value A
Reset value B
Control value A
Reset value B
FDCW71VNX
13
12
13
12
FDCW100VNX
Fig. C
Fig. C
Fig. C
Fig. C
FDCW140VNX
7) Power transistor temperature control
This control monitors the power transistor temperature (TIP) from the start operation of compressor, and when the
following condition is established, compressor speed (frequency) is controlled.
Power transistor temperature (°C)
Reset
Retention
Reduce compressor speed
at every 1 minute.
77
80
70
73
FDCW100VNX
81
85
FDCW71VNX
FDCW140VNX
Operation control function by the outdoor unit control
Summary of Contents for FDCW100VNX-A
Page 7: ... 5 Technical data 19 HM T 340 Technical data ...
Page 36: ... 34 Technical data 19 HM T 340 Dimensions FDCW71VNX A Meaning of symbol ...
Page 38: ... 36 Technical data 19 HM T 340 FDCW140VNX A Meaning of symbol Dimensions ...
Page 41: ... 39 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 42: ... 40 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 43: ... 41 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 44: ... 42 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 45: ... 43 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 46: ... 44 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 47: ... 45 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 48: ... 46 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 49: ... 47 Technical data 19 HM T 340 Electrical circuit diagram Split box HSB60 W ...
Page 50: ... 48 Technical data 19 HM T 340 HSB100 Electrical circuit diagram ...
Page 51: ... 49 Technical data 19 HM T 340 HSB140 Electrical circuit diagram ...
Page 52: ... 50 Technical data 19 HM T 340 Electrical circuit diagram Outdoor units FDCW60VNX A ...
Page 57: ... 55 Technical data 19 HM T 340 Electrical circuit diagram POWER SOURCE RC HY20 W sheet 3 ...
Page 58: ... 56 Technical data 19 HM T 340 Electrical circuit diagram RC HY20 W sheet 4 ...
Page 61: ... 59 Technical data 19 HM T 340 Electrical circuit diagram POWER SOURCE RC HY40 W sheet 3 ...
Page 62: ... 60 Technical data 19 HM T 340 Electrical circuit diagram RC HY40 W sheet 4 ...
Page 64: ... 62 Technical data 19 HM T 340 Electrical circuit diagram RC HY40 W sheet 6 ...
Page 65: ...Installation 19 HM T 340 Installation 63 ...
Page 133: ...Control 19 HM T 340 Control 131 ...
Page 170: ... 168 Service 19 HM T 340 Service ...
Page 263: ... 258 Service 19 HM T 340 Outdoor unit FDCW60VNX FDCW71VNX Component replacement ...
Page 264: ...Service 259 19 HM T 340 FDCW100VNX FDCW140VNX LEK LEK Component replacement ...
Page 290: ... 285 Components 19 HM T 340 Components ...
Page 300: ... 295 Components 19 HM T 340 PT300 Component positions ...
Page 301: ... 296 Components 19 HM T 340 Component positions PT300 PT300 A mm 1634 B mm 743 C mm 673 ...
Page 302: ... 297 Components 19 HM T 340 PT500 Component positions ...
Page 303: ... 298 Components 19 HM T 340 PT500 Component positions PT500 A mm 1835 B mm 897 C mm 832 ...
Page 311: ...THo R THo A THo D Outside units FDCW60VNX 306 Components 19 HM T 340 Piping system ...