Installation
'19 • HM-T-340
Pipe installation
General
A following table shows plumbing necessary for each product.
Refrigerant
Plumbing
HSB
Necessary
Necessary
HMA-S
Necessary
Necessary
PT
-
Necessary
PC-HY
-
-
Outdoor unit
AA25
P
Indoor unit
BP4
BT3
BT15
BT12
XL14
XL13
XL1
XL2
Storage tank
Pipe installation must be carried out in accordance with current norms and directives.
This heat pump system is designed for low or medium temperature heating system. It is recommended water temperature must not
exceed 55°C on supply and 45°C on return at lowest design outdoor temperature (DOT) though indoor unit can operate with a return
temperature of up to 65°C and an outgoing temperature from the unit of 65°C.
Indoor unit is not equipped with shut off valves; these must be installed outside the heat pump to facilitate any future servicing.
Indoor unit can be connected to the radiator system, floor heating system and/or fan convectors.
Safety valve is not equipped with in indoor unit. Make sure to install safety valve in the circuit.
Installation diagram
FDCW series outdoor unit provides heat for space heating and domestic hot water using free energy in the outdoor air within the range
of low temperature up to -20°C. Connection is different according to the type of indoor unit (see below figures). The system is
controlled by RC-HY20-W or RC-HY40-W control unit.
HSB series
HSB series indoor unit is equipped with plate heat exchanger. It needs to install expansion vessel, shut-o
ff
valves, safety valve,
electric heater and circulation pump to make a complete heating system. In case domestic hot water is required, 3-way valve and tank
is also necessary.
Indoor unit installation
- 80 -
#
Summary of Contents for FDCW100VNX-A
Page 7: ... 5 Technical data 19 HM T 340 Technical data ...
Page 36: ... 34 Technical data 19 HM T 340 Dimensions FDCW71VNX A Meaning of symbol ...
Page 38: ... 36 Technical data 19 HM T 340 FDCW140VNX A Meaning of symbol Dimensions ...
Page 41: ... 39 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 42: ... 40 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 43: ... 41 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 44: ... 42 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 45: ... 43 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 46: ... 44 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 47: ... 45 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 48: ... 46 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 49: ... 47 Technical data 19 HM T 340 Electrical circuit diagram Split box HSB60 W ...
Page 50: ... 48 Technical data 19 HM T 340 HSB100 Electrical circuit diagram ...
Page 51: ... 49 Technical data 19 HM T 340 HSB140 Electrical circuit diagram ...
Page 52: ... 50 Technical data 19 HM T 340 Electrical circuit diagram Outdoor units FDCW60VNX A ...
Page 57: ... 55 Technical data 19 HM T 340 Electrical circuit diagram POWER SOURCE RC HY20 W sheet 3 ...
Page 58: ... 56 Technical data 19 HM T 340 Electrical circuit diagram RC HY20 W sheet 4 ...
Page 61: ... 59 Technical data 19 HM T 340 Electrical circuit diagram POWER SOURCE RC HY40 W sheet 3 ...
Page 62: ... 60 Technical data 19 HM T 340 Electrical circuit diagram RC HY40 W sheet 4 ...
Page 64: ... 62 Technical data 19 HM T 340 Electrical circuit diagram RC HY40 W sheet 6 ...
Page 65: ...Installation 19 HM T 340 Installation 63 ...
Page 133: ...Control 19 HM T 340 Control 131 ...
Page 170: ... 168 Service 19 HM T 340 Service ...
Page 263: ... 258 Service 19 HM T 340 Outdoor unit FDCW60VNX FDCW71VNX Component replacement ...
Page 264: ...Service 259 19 HM T 340 FDCW100VNX FDCW140VNX LEK LEK Component replacement ...
Page 290: ... 285 Components 19 HM T 340 Components ...
Page 300: ... 295 Components 19 HM T 340 PT300 Component positions ...
Page 301: ... 296 Components 19 HM T 340 Component positions PT300 PT300 A mm 1634 B mm 743 C mm 673 ...
Page 302: ... 297 Components 19 HM T 340 PT500 Component positions ...
Page 303: ... 298 Components 19 HM T 340 PT500 Component positions PT500 A mm 1835 B mm 897 C mm 832 ...
Page 311: ...THo R THo A THo D Outside units FDCW60VNX 306 Components 19 HM T 340 Piping system ...