Control
‘19 • HM-T-340
CAUTION
Curve 0 in menu 1.9.1 must be selected for own curve to
apply.
Menu 1.9.8 - point offset
point offset
1.9.8
change in curve
outdoor temp. point
°C
°C
outdoor temp. °C
flow temperature °C
outdoor temp. point
Setting range: -40 – 30 °C
Default value: 0 °C
change in curve
Setting range: -10 – 10 °C
Default value: 0 °C
Select a change in the heating curve at a certain outdoor
temperature here. One step is usually enough to change the
room temperature by one degree, but in some cases several
steps may be required.
The heat curve is affected at ± 5 °C from set outdoor temp.
point.
It is important that the correct heating curve is selected so that
the room temperature is experienced as even.
TIP
If it is cold in the house, at, for example -2 °C, "outdoor temp.
point" is set to "-2" and "change in curve" is increased until
the desired room temperature is maintained.
CAUTION
Wait 24 hours before making a new setting, so that the
room temperat- ure has time to stabilise.
step difference compressors (RC-HY40
-W/HMA-S
only)
CAUTION
supply temperature
own heating curve
1.9.7.1
flow line temp. at -20 °C
flow line temp. at -10 °C
flow line temp. at 0 °C
flow line temp. at 10 °C
flow line temp. at -30 °C
flow line temp. at 20 °C
°C
°C
°C
°C
°C
°C
own cooling curve
1.9.7.2
flow line temp. at 10 °C
flow line temp. at 20 °C
flow line temp. at 30 °C
flow line temp. at 40 °C
flow line temp. at 0 °C
°C
°C
°C
°C
°C
20
20
20
20
20
heating
Setting range: 5 – 70 °C
cooling (accessory required)
Depending on which accessory is used the setting range can
vary.
Setting range: -5 – 40 °C
Create your own heating or cooling curve here, by setting the
desired supply temperatures for diff erent outdoor temperatures.
This setting option only appears if cooling is activated in
menu 5.2.4.
The degree minute difference for controlling when the next
compressor is to start is set here.
degree minutes cooling (
RC-HY40-W/HMA-S
only)
This selection is only available when the connected accessory
itself counts cooling degree minutes.
After a min. or max. value has been set, the system
will automatically set the real value in relation to the
number of compressors that are running cooling.
time betw. switch heat/cool
This selection is only available in cooling 2-pipe systems.
Here you can set how long RC-HY20/40
-W and HMA-S
is
to wait before it returns to heating mode when the cooling
demand has ceased or vice versa.
Menu 1.9.7 - own curve
Control
- 145 -
#
Summary of Contents for FDCW100VNX-A
Page 7: ... 5 Technical data 19 HM T 340 Technical data ...
Page 36: ... 34 Technical data 19 HM T 340 Dimensions FDCW71VNX A Meaning of symbol ...
Page 38: ... 36 Technical data 19 HM T 340 FDCW140VNX A Meaning of symbol Dimensions ...
Page 41: ... 39 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 42: ... 40 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 43: ... 41 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 44: ... 42 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 45: ... 43 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 46: ... 44 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 47: ... 45 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 48: ... 46 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 49: ... 47 Technical data 19 HM T 340 Electrical circuit diagram Split box HSB60 W ...
Page 50: ... 48 Technical data 19 HM T 340 HSB100 Electrical circuit diagram ...
Page 51: ... 49 Technical data 19 HM T 340 HSB140 Electrical circuit diagram ...
Page 52: ... 50 Technical data 19 HM T 340 Electrical circuit diagram Outdoor units FDCW60VNX A ...
Page 57: ... 55 Technical data 19 HM T 340 Electrical circuit diagram POWER SOURCE RC HY20 W sheet 3 ...
Page 58: ... 56 Technical data 19 HM T 340 Electrical circuit diagram RC HY20 W sheet 4 ...
Page 61: ... 59 Technical data 19 HM T 340 Electrical circuit diagram POWER SOURCE RC HY40 W sheet 3 ...
Page 62: ... 60 Technical data 19 HM T 340 Electrical circuit diagram RC HY40 W sheet 4 ...
Page 64: ... 62 Technical data 19 HM T 340 Electrical circuit diagram RC HY40 W sheet 6 ...
Page 65: ...Installation 19 HM T 340 Installation 63 ...
Page 133: ...Control 19 HM T 340 Control 131 ...
Page 170: ... 168 Service 19 HM T 340 Service ...
Page 263: ... 258 Service 19 HM T 340 Outdoor unit FDCW60VNX FDCW71VNX Component replacement ...
Page 264: ...Service 259 19 HM T 340 FDCW100VNX FDCW140VNX LEK LEK Component replacement ...
Page 290: ... 285 Components 19 HM T 340 Components ...
Page 300: ... 295 Components 19 HM T 340 PT300 Component positions ...
Page 301: ... 296 Components 19 HM T 340 Component positions PT300 PT300 A mm 1634 B mm 743 C mm 673 ...
Page 302: ... 297 Components 19 HM T 340 PT500 Component positions ...
Page 303: ... 298 Components 19 HM T 340 PT500 Component positions PT500 A mm 1835 B mm 897 C mm 832 ...
Page 311: ...THo R THo A THo D Outside units FDCW60VNX 306 Components 19 HM T 340 Piping system ...