Control
'19 • HM-T-340
Flow line temperature – maximum and minimum
values
This function is used in order to limit max-min supply
temperature. The heating / cooling curve becomes fl at beyond
max / min target temperature.
CAUTION
Underfloor heating systems are normally "max flow line
temperature" set between 35 and 45°C. Take care not to
cause low temperature burns in case it is set higher than
35°C.
Must be restricted with underfloor cooling min. flow line
temp. to prevent condensation.
Check the max temperature for your floor with your
installer/floor supplier.
30
40
50
60
70
°C
- 40 °C
UTETEMPERATUR
- 10
0
10
- 20
- 30
Maximivärde
Minimivärde
Supply temperature
Outdoor temperature
Maximum value
Minimum value
The fi gure at the end of the curve indicates the curve number.
The fi gure beside the thermometer icon gives the curve off set.
Use the control knob to set a new value.
Confi rm the new setting by pressing the OK button.
Curve 0 is an own curve created in menu 1.9.7.
To select another curve (slope):
1.
Press OK button to access the setting mode.
2.
Select a new curve. The curves are numbered from 0
to 15, and the bigger number curve has steeper slope.
Curve 0 means that "own curve" (menu 1.9.7) is
used.
3.
Press OK button to exit the setting.
To read off a curve:
1.
Turn the control knob so that the ring on the shaft
with the outdoor temperature is marked.
2. Press OK button.
3.
Follow the grey line up to the curve and out to the
left to read off the value for the supply temperature
at the selected outdoor temperature.
4.
You can now select to take read outs for different
outdoor temperatures by turning the control knob to
the right or left and read off the corresponding fl ow
temperature.
5. Press OK or Back button to exit read off mode.
TIP
Wait 24 hours before making a new setting, so that the
room temperature has time to stabilise.
If it is cold outdoors and the room temperature is too low,
increase the curve slope by one increment.
If it is cold outdoors and the room temperature is too high,
lower the curve slope by one increment.
If it is warm outdoors and the room temperature is too low,
increase the curve offset by one increment.
If it is warm outdoors and the room temperature is too high,
lower the curve offset by one increment.
Menu 1.9.2 - external adjustment
external adjustment
1.9.2
climate system 1
climate system 2
climate system 3
climate system 4
°C
°C
.
y
l
n
o
"
1
m
e
ts
y
s
e
t
a
m
il
c
"
s
w
o
h
s
y
a
l
p
si
d
,
m
e
ts
y
s
e
t
a
m
il
c
e
n
o
s
i
e
r
e
h
t
fI
*
climate system
Setting range: -10 to +10 or desired room temperature if the
room sensor is installed.
Default value: 0
Connecting an external contact, for example, a room thermostat
or a timer allows you to temporarily or periodically increase or
decrease the room temperature while heating. When the contact
is on, the heating curve offset is changed by the number of
steps selected in the menu. If a room sensor is installed and
activated the desired room temperature (°C) is set.
If there is more than one climate system the setting can be
made separately for each system.
Control
- 142 -
Summary of Contents for FDCW100VNX-A
Page 7: ... 5 Technical data 19 HM T 340 Technical data ...
Page 36: ... 34 Technical data 19 HM T 340 Dimensions FDCW71VNX A Meaning of symbol ...
Page 38: ... 36 Technical data 19 HM T 340 FDCW140VNX A Meaning of symbol Dimensions ...
Page 41: ... 39 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 42: ... 40 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 43: ... 41 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 44: ... 42 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 45: ... 43 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 46: ... 44 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 47: ... 45 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 48: ... 46 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 49: ... 47 Technical data 19 HM T 340 Electrical circuit diagram Split box HSB60 W ...
Page 50: ... 48 Technical data 19 HM T 340 HSB100 Electrical circuit diagram ...
Page 51: ... 49 Technical data 19 HM T 340 HSB140 Electrical circuit diagram ...
Page 52: ... 50 Technical data 19 HM T 340 Electrical circuit diagram Outdoor units FDCW60VNX A ...
Page 57: ... 55 Technical data 19 HM T 340 Electrical circuit diagram POWER SOURCE RC HY20 W sheet 3 ...
Page 58: ... 56 Technical data 19 HM T 340 Electrical circuit diagram RC HY20 W sheet 4 ...
Page 61: ... 59 Technical data 19 HM T 340 Electrical circuit diagram POWER SOURCE RC HY40 W sheet 3 ...
Page 62: ... 60 Technical data 19 HM T 340 Electrical circuit diagram RC HY40 W sheet 4 ...
Page 64: ... 62 Technical data 19 HM T 340 Electrical circuit diagram RC HY40 W sheet 6 ...
Page 65: ...Installation 19 HM T 340 Installation 63 ...
Page 133: ...Control 19 HM T 340 Control 131 ...
Page 170: ... 168 Service 19 HM T 340 Service ...
Page 263: ... 258 Service 19 HM T 340 Outdoor unit FDCW60VNX FDCW71VNX Component replacement ...
Page 264: ...Service 259 19 HM T 340 FDCW100VNX FDCW140VNX LEK LEK Component replacement ...
Page 290: ... 285 Components 19 HM T 340 Components ...
Page 300: ... 295 Components 19 HM T 340 PT300 Component positions ...
Page 301: ... 296 Components 19 HM T 340 Component positions PT300 PT300 A mm 1634 B mm 743 C mm 673 ...
Page 302: ... 297 Components 19 HM T 340 PT500 Component positions ...
Page 303: ... 298 Components 19 HM T 340 PT500 Component positions PT500 A mm 1835 B mm 897 C mm 832 ...
Page 311: ...THo R THo A THo D Outside units FDCW60VNX 306 Components 19 HM T 340 Piping system ...