Control
‘19 • HM-T-340
Day:
Select which day or days of the week the schedule is to
apply to here. To remove the scheduling for a particular day,
the time for that day must be reset by setting the start time to
the same as the stop time. If the line "all" is used, all days in
the period are set for these times.
Time period:
The start and stop time for the selected day for
scheduling are selected here.
Blocking:
The desired blocking is selected here.
Conflict:
If two settings conflict with each other a red
exclamation mark is displayed.
Blocking the compressor in the outdoor unit.
Blocking additional heat.
TIP
If you wish to set similar scheduling for every day of the
week start by filling in “all” and then changing the desired
days.
TIP
Set the stop time earlier than the start time so that the
period extends beyond midnight. Scheduling then stops at
the set stop time the day after.
Scheduling always starts on the date that the start time is
set for.
CAUTION
Long term blocking can cause reduced comfort and
operating economy.
Menu 4.9.6 - schedule silent mode
The compressor can be scheduled to be set to "silent mode" (the
heat pump must support this) for up to two different time
periods here.
When scheduling is active the "silent mode" symbol is shown
in the main menu on the symbol for the control module.
activated
schedule 2
schedule 1
all
mon
tues
wed
thur
fri
sat
sun
schedule silent mode
4.9.6
Time period
Day
Activated
Schedule
Conflict
Factory setting: 400
diff. between additional steps
Setting range: 10 – 1000
Factory setting: 30
Degree minutes are a measurement of the current heating
requirement in the house and determine when the compressor
respectively additional heat will start/stop.
CAUTION
Higher value on "start compressor" gives more compressor
starts, which increase wear on the compressor. Too low
value can give uneven indoor temperatures.
Menu 4.9.4 - factory setting user
All settings that are available to the user (including advanced
menus) can be reset to default values here.
Do you want to reset all user settings to
factory settings?
factory setting user
4.9.4
yes
no
CAUTION
After factory setting, personal settings such as heating
curves must be reset.
Menu 4.9.5 - schedule blocking
The additional heat can be scheduled to be blocked for up to
two diff erent time periods here.
activated
schedule 2
schedule 1
all
mon
tues
wed
thur
fri
sat
sun
schedule blocking
4.9.5
Activated
Schedule
Time period Blocking
Day
Conflict
When scheduling is active the relevant blocking symbol is
shown in the main menu on the symbol for the control module.
Schedule:
The period to be changed is selected here.
Activated:
Scheduling for the selected period is activated
here. Set times are not aff ected at deactivation.
Control
- 159 -
Summary of Contents for FDCW100VNX-A
Page 7: ... 5 Technical data 19 HM T 340 Technical data ...
Page 36: ... 34 Technical data 19 HM T 340 Dimensions FDCW71VNX A Meaning of symbol ...
Page 38: ... 36 Technical data 19 HM T 340 FDCW140VNX A Meaning of symbol Dimensions ...
Page 41: ... 39 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 42: ... 40 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 43: ... 41 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 44: ... 42 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 45: ... 43 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 46: ... 44 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 47: ... 45 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 48: ... 46 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 49: ... 47 Technical data 19 HM T 340 Electrical circuit diagram Split box HSB60 W ...
Page 50: ... 48 Technical data 19 HM T 340 HSB100 Electrical circuit diagram ...
Page 51: ... 49 Technical data 19 HM T 340 HSB140 Electrical circuit diagram ...
Page 52: ... 50 Technical data 19 HM T 340 Electrical circuit diagram Outdoor units FDCW60VNX A ...
Page 57: ... 55 Technical data 19 HM T 340 Electrical circuit diagram POWER SOURCE RC HY20 W sheet 3 ...
Page 58: ... 56 Technical data 19 HM T 340 Electrical circuit diagram RC HY20 W sheet 4 ...
Page 61: ... 59 Technical data 19 HM T 340 Electrical circuit diagram POWER SOURCE RC HY40 W sheet 3 ...
Page 62: ... 60 Technical data 19 HM T 340 Electrical circuit diagram RC HY40 W sheet 4 ...
Page 64: ... 62 Technical data 19 HM T 340 Electrical circuit diagram RC HY40 W sheet 6 ...
Page 65: ...Installation 19 HM T 340 Installation 63 ...
Page 133: ...Control 19 HM T 340 Control 131 ...
Page 170: ... 168 Service 19 HM T 340 Service ...
Page 263: ... 258 Service 19 HM T 340 Outdoor unit FDCW60VNX FDCW71VNX Component replacement ...
Page 264: ...Service 259 19 HM T 340 FDCW100VNX FDCW140VNX LEK LEK Component replacement ...
Page 290: ... 285 Components 19 HM T 340 Components ...
Page 300: ... 295 Components 19 HM T 340 PT300 Component positions ...
Page 301: ... 296 Components 19 HM T 340 Component positions PT300 PT300 A mm 1634 B mm 743 C mm 673 ...
Page 302: ... 297 Components 19 HM T 340 PT500 Component positions ...
Page 303: ... 298 Components 19 HM T 340 PT500 Component positions PT500 A mm 1835 B mm 897 C mm 832 ...
Page 311: ...THo R THo A THo D Outside units FDCW60VNX 306 Components 19 HM T 340 Piping system ...