Control
‘19 • HM-T-340
Menu 5.1 - operating settings
Operating settings can be made for the control module in the
sub-menus.
Menu 5.1.1 - hot water settings
economy
Setting range start temp. economy: 5 – 55 °C
Factory setting start temp. economy: 42 °C
Setting range stop temp. economy: 5 – 60 °C
Factory setting stop temp. economy: 48 °C
normal
Setting range start temp. normal: 5 – 60 °C
Factory setting start temp. normal: 46 °C
Setting range stop temp. normal: 5 – 65 °C
Factory setting stop temp. normal: 50 °C
luxury
Setting range start temp. lux: 5 – 70 °C
Factory setting start temp. lux: 49 °C
Setting range stop temp. lux: 5 – 70 °C
Factory setting stop temp. lux: 53 °C
stop temp. per. increase
Setting range: 55 – 70 °C
Factory setting: 55 °C
charge method
Setting range: target temp, delta temp
Default value: delta temp
Here you set the start and stop temperature of the hot water for
the diff erent comfort options in menu 2.2 as well as the stop
temperature for periodic increase in menu 2.9.1.
The charge method for hot water mode is selected here. "delta
temp" is recommended for heaters with charge coil, "target
temp" for heaters with domestic coil.
Menu 5.1.2 - max flow line temperature
climate system
Setting range: 5 – 70 °C
Default value: 60 °C
Set the maximum supply temperature for the climate system
here. If the installation has more than one climate system,
individual maximum supply temperatures can be set for each
system. Climate systems 2 – 8 cannot be set to a higher max
supply temperature than climate system 1.
CAUTION
Underfloor heating systems are normally max flow line
temperature set between 35 and 45°C.
Be careful not to cause low temperature burn if it is set at
35°C or higher.
Check the max floor temperature with your floor supplier.
Sub-menus
Menu SERVICE has orange text and is intended for the
advanced user. This menu has several sub-menus.
Status information for the relevant menu can be found on the
display to the right of the menus.
operating settings:
Operating settings for the control
module.
system settings:
System settings for the control module,
activating accessories etc.
soft in/outputs:
Setting software controlled in and
outputs on the input card (AA3) and terminal block (X2).
factory setting service:
Total reset of all settings (including
settings available to the user ) to default values.
forced control:
Forced control of the diff erent components in
the indoor module.
start guide:
Manual start of the start guide which is run the
fi rst time when the control module is started.
quick start:
Quick starting the compressor.
NOTE
Incorrect settings in the service menus can damage the
installation.
Control
- 161 -
Summary of Contents for FDCW100VNX-A
Page 7: ... 5 Technical data 19 HM T 340 Technical data ...
Page 36: ... 34 Technical data 19 HM T 340 Dimensions FDCW71VNX A Meaning of symbol ...
Page 38: ... 36 Technical data 19 HM T 340 FDCW140VNX A Meaning of symbol Dimensions ...
Page 41: ... 39 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 42: ... 40 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 43: ... 41 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 44: ... 42 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 45: ... 43 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 46: ... 44 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 47: ... 45 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 48: ... 46 Technical data 19 HM T 340 Electrical circuit diagram ...
Page 49: ... 47 Technical data 19 HM T 340 Electrical circuit diagram Split box HSB60 W ...
Page 50: ... 48 Technical data 19 HM T 340 HSB100 Electrical circuit diagram ...
Page 51: ... 49 Technical data 19 HM T 340 HSB140 Electrical circuit diagram ...
Page 52: ... 50 Technical data 19 HM T 340 Electrical circuit diagram Outdoor units FDCW60VNX A ...
Page 57: ... 55 Technical data 19 HM T 340 Electrical circuit diagram POWER SOURCE RC HY20 W sheet 3 ...
Page 58: ... 56 Technical data 19 HM T 340 Electrical circuit diagram RC HY20 W sheet 4 ...
Page 61: ... 59 Technical data 19 HM T 340 Electrical circuit diagram POWER SOURCE RC HY40 W sheet 3 ...
Page 62: ... 60 Technical data 19 HM T 340 Electrical circuit diagram RC HY40 W sheet 4 ...
Page 64: ... 62 Technical data 19 HM T 340 Electrical circuit diagram RC HY40 W sheet 6 ...
Page 65: ...Installation 19 HM T 340 Installation 63 ...
Page 133: ...Control 19 HM T 340 Control 131 ...
Page 170: ... 168 Service 19 HM T 340 Service ...
Page 263: ... 258 Service 19 HM T 340 Outdoor unit FDCW60VNX FDCW71VNX Component replacement ...
Page 264: ...Service 259 19 HM T 340 FDCW100VNX FDCW140VNX LEK LEK Component replacement ...
Page 290: ... 285 Components 19 HM T 340 Components ...
Page 300: ... 295 Components 19 HM T 340 PT300 Component positions ...
Page 301: ... 296 Components 19 HM T 340 Component positions PT300 PT300 A mm 1634 B mm 743 C mm 673 ...
Page 302: ... 297 Components 19 HM T 340 PT500 Component positions ...
Page 303: ... 298 Components 19 HM T 340 PT500 Component positions PT500 A mm 1835 B mm 897 C mm 832 ...
Page 311: ...THo R THo A THo D Outside units FDCW60VNX 306 Components 19 HM T 340 Piping system ...