VII
Control ]
- 143 -
HWE09130
GB
(2) ME remote controller (PAR-F27MEA-US)
Set the address of the remote controller with the rotary switch.
To set addresses, use a precision slotted screw driver [2.0 mm [0.08 in] (w)], and do not apply than 19.6N.
The use of any other tool or applying too much load may damage the switch.
4. Switch functions <BC controller> (Control board)
012
3
45
67
8
9
012
3
45
67
8
9
012
3
45
67
8
9
012
3
45
67
8
9
10's digit 1's digit
(left)
(right)
Remote controller unit
Rotary switch
Example: In case of address 108
Address setting range
Setting method
Main remote controller
101-150
Add 100 to the smallest address of all the indoor units in the
same group.
Sub remote controller
151-200
Add 150 to the smallest address of all the indoor units in the
same group.
Setting of rotary switch
Address No.
01-99
*1
101-199 with the 100's digit automatically being set to 1
*2
00
200
*1. At factory shipment, the rotary switch is set to 01.
*2. The address range that can be set with the ME remote controller is between 101 and 200. When the dials are set to
a number between 01 and 99, the 100's digit is automatically set to [1]. When the dials are set to 00, the 100's digit is
automatically set to [2].
Switch
Function
Function according to switch setting
Switch setting timing
OFF
ON
SW4
1
Model setting
R410A
-
Always leave this switch to OFF.
2 - 5
-
-
-
-
6
No. of ports
*1
*1. When a junction pipe kit was used to merge two ports to connect the indoor units with a total capacity of between P31
and P54, turn DIP SW4-6 to ON. When connecting a main and a sub BC controller, change the SW setting on only the
main BC controller. (It is not necessary to change the SW setting on the sub BC controller. )
1
2
Before being energized
7, 8
-
-
-
-
SW5
1 - 6
-
-
-
-
7
-
-
-
-
8
-
-
-
-
Summary of Contents for PURY-P120
Page 1: ...Models PURY P72 P96 P120 P144T Y JMU A PURY P168 P192 P216 P240 P264 P288T Y SJMU A ...
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 36: ... II Restrictions 27 HWE09130 GB ...
Page 50: ... II Restrictions 41 41 HWE09130 GB ...
Page 67: ... 58 II Restrictions GB HWE09130 ...
Page 69: ... 60 ...
Page 95: ... 86 III Outdoor Unit Components GB HWE09130 ...
Page 97: ... 88 ...
Page 105: ... 96 IV Remote Controller GB HWE09130 ...
Page 107: ... 98 ...
Page 125: ... 116 ...
Page 145: ... 136 ...
Page 175: ... 166 VII Control GB HWE09130 ...
Page 177: ... 168 ...
Page 203: ... 194 ...
Page 363: ... 354 IX Troubleshooting GB HWE09130 ...
Page 365: ... 356 ...