VIII
Test Run Mode ]
- 183 -
HWE09130
GB
Operation
Outdoor unit model
PURY-P216TSJMU-A
PURY-P120TJMU-A
PURY-P96TJMU-A
Model name of BC controller
CMB-P1013NU-GA
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
26.7°C/19.4°C [80 °F/67 °F]
Outdoor
35°C/ [95 °F/]
Indoor unit
No. of connected units
Unit
6
No. of units in operation
6
Model
-
36/36/36/36/36/36
Piping
Main pipe
m
[ft]
5 [16-3/8"]
Branch pipe
10 [32-3/4"]
Total pipe length
65 [213-1/4"]
Fan speed
-
Hi
Amount of refrigerant
kg
[lbs-oz]
43.0 [95]
Outdoor
unit
Electric current
A
51.0
Voltage
V
230
Compressor frequency
Hz
75
61
LEV open-
ing
Indoor unit
Pulse
275/275/275/275/275/275
BC controller (1/2/3)
2000/2000/280
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
2.82/0.92
[409/133]
2.78/0.92
[403/133]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.73/2.72
[395/394]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
82 [180]
82 [180]
Heat exchanger outlet
(TH3)
43 [109]
39 [102]
Accumulator inlet
8 [46]
8 [46]
Accumulator outlet
8 [46]
8 [46]
Compressor inlet
20 [68]
19 [66]
Compressor shell bottom
42 [108]
40 [104]
Indoor unit
LEV inlet
22 [72]
Heat exchanger inlet
9 [48]
Summary of Contents for PURY-P120
Page 1: ...Models PURY P72 P96 P120 P144T Y JMU A PURY P168 P192 P216 P240 P264 P288T Y SJMU A ...
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 36: ... II Restrictions 27 HWE09130 GB ...
Page 50: ... II Restrictions 41 41 HWE09130 GB ...
Page 67: ... 58 II Restrictions GB HWE09130 ...
Page 69: ... 60 ...
Page 95: ... 86 III Outdoor Unit Components GB HWE09130 ...
Page 97: ... 88 ...
Page 105: ... 96 IV Remote Controller GB HWE09130 ...
Page 107: ... 98 ...
Page 125: ... 116 ...
Page 145: ... 136 ...
Page 175: ... 166 VII Control GB HWE09130 ...
Page 177: ... 168 ...
Page 203: ... 194 ...
Page 363: ... 354 IX Troubleshooting GB HWE09130 ...
Page 365: ... 356 ...