VI
Refrigerant Circuit ]
- 128 -
HWE09130
GB
Heater
CH11
Heats the refrigerant in the com-
pressor
Belt heater
P72 model
1511 ohm 35W
P96, P120, P144 models
1280 ohm 45W
Resistance
check
4-way
valve
21S4a
Changeover between heating and
cooling
AC208-230V
Dead: cooling cycle
Live: heating cycle
Continuity
check with a
tester
Fan mo-
tor
FAN motor 1,2
FAN
motor 2
is only
on the
P120
and
P144
mod-
els.
Regulates the heat exchanger ca-
pacity by adjusting the operating
frequency and operating the pro-
peller fan based on the operating
pressure.
(TJMU)
AC180V, 50.5Hz, 920W
(YJMU)
AC414V, 50.5Hz, 920W
Part
name
Symbols
(functions)
Notes
Usage
Specifications
Check method