II
Restrictions ]
- 57 -
HWE09130
GB
(3) Size of the pipe that fits the sub BC controller ports
The ports of the BC controller accommodates the pipes on P24 - P54 models of indoor units. To connect other types of indoor
units, follow the procedure below.
1) To connect P06 - P18 models of indoor units use the reducer that is supplied with the BC controller.
2) To connect the P72 through P96 models of indoor units (or when the total capacity of indoor units is P55 or above), use
an optional twinning pipe kit (Model: CMY-R160-J) to merge two ports before connecting them.
3) To connect multiple indoor units to a port (or to a junction pipe)
Maximum total capacity of connected indoor units: P54 or below (in a system with a junction pipe: P96 or below)
Maximum number of connectable indoor units: 3 units
Branch joint: Use CMY-Y102S-G2 (optional accessory).
Refrigerant pipe selection (size of the pipes in sections A and B in the figure above): Select the proper based on the total
capacity of the downstream indoor units, using the table below as a reference.
Unit : mm [inch]
Total capacity of indoor units
Liquid pipe
Gas pipe
P54 or below
ø9.52 [3/8"]
ø15.88 [5/8"]
P55 - P72
ø9.52 [3/8"]
ø19.05 [3/4"]
P73 - P96
ø9.52 [3/8"]
ø22.2 [7/8"]
Unit : mm [inch]
Operation
Pipe sections
High-pressure side
(liquid)
Low-pressure side
(gas)
Liquid pipe side
Total capacity of the in-
door units that are con-
nected to the BC
controller
On the BC controller
side
P72 model or below
ø15.88 [5/8"]
(Brazed connection)
ø19.05 [3/4"]
(Brazed connection)
ø9.52 [3/8"]
(Brazed connection)
P73 - P108
ø19.05 [3/4"]
(Brazed connection)
ø22.2 [7/8"]
(Brazed connection)
P109 - P126
ø28.58 [1-1/8"]
(Brazed connection)
ø12.7 [1/2"]
(Brazed connection)
P127 - P144
ø22.2 [7/8"]
(Brazed connection)
P145 - P168
ø15.88 [5/8"]
(Brazed connection)
A
B
Indoor
Indoor
Indoor
P18 model or below P24 - P54 models P72 - P96 models
*2
Junction pipe kit
(Model name:
CMY-R160-J)
(Optional accessory)
BC controller (sub)
To Main BC controller
Connection: Brazed connection
*1
Reducer
(Standard supplied parts)
Maximum of 3 units per port
Total capacity of P54 or below
(All units connected to the same port
must be in the same operating mode.)
3*
Indoor
Indoor
Indoor
Branch joint (Model name:CMY-Y102S-G2)
(Optional
accessory)
Summary of Contents for PURY-P120
Page 1: ...Models PURY P72 P96 P120 P144T Y JMU A PURY P168 P192 P216 P240 P264 P288T Y SJMU A ...
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 36: ... II Restrictions 27 HWE09130 GB ...
Page 50: ... II Restrictions 41 41 HWE09130 GB ...
Page 67: ... 58 II Restrictions GB HWE09130 ...
Page 69: ... 60 ...
Page 95: ... 86 III Outdoor Unit Components GB HWE09130 ...
Page 97: ... 88 ...
Page 105: ... 96 IV Remote Controller GB HWE09130 ...
Page 107: ... 98 ...
Page 125: ... 116 ...
Page 145: ... 136 ...
Page 175: ... 166 VII Control GB HWE09130 ...
Page 177: ... 168 ...
Page 203: ... 194 ...
Page 363: ... 354 IX Troubleshooting GB HWE09130 ...
Page 365: ... 356 ...