IX
Troubleshooting ]
- 254 -
HWE09130
GB
1. Error
Code
No ACK error
2. Error definition and error detection method
The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans-
mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide
the response (ACK).
3. System
configuration
(3) System connected to the system controllers (MELANS)
6607
Error
source
address
Error display
Detection
method
Cause
Check method and remedy
Indoor
unit
(IC)
ME remote
controller (RC)
MA remote
controller (MA)
No acknowl-
edgement
(ACK) at RC
transmis-
sion to IC
Same as grouping of units in a system
with multiple outdoor units
Same remedy as that for
grouping of units in a sys-
tem with multiple outdoor
units
System control-
ler (SC)
No acknowl-
edgement
(ACK) at SC
transmis-
sion to IC
1.
Error occurrence on some IC
Same remedy as that for
system with one outdoor
unit
(1)
Same cause as that for system with one
outdoor unit
2.
Error occurrence on all IC in the system
with one outdoor unit
1)
Check the LED display
for troubleshooting on the
outdoor unit.
(1)
Total capacity error (7100)
If an error is found,
check the check code
definition, and correct
the error.
If no error is found,
check 2).
(2)
Capacity code error (7101)
(3)
Error in the number of connected units
(7102)
(4)
Address setting error (7105)
(5)
Disconnection or short circuit of the trans-
mission line for the outdoor unit on the ter-
minal block for centralized control line
connection (TB7)
2)
Check (5) - (7) on the left.
(6)
Turn off the power source of the outdoor
unit
(7)
Malfunction of electrical system for the
outdoor unit
3.
Error occurrence on all IC
Check voltage of the
transmission line for cen-
tralized control.
20V or more: Check (1)
and (2) on the left.
Less than 20V: Check
(3) on the left.
(1)
Same causes as (1) - (7) described in 2.
(2)
The male power supply connectors on 2
or more outdoor units are connected to
the female power supply switch connector
(CN40) for the transmission line for cen-
tralized control.
(3)
Disconnection or shutdown of the power
source of the power supply unit for trans-
mission line
(4)
System controller (MELANS) malfunction
Summary of Contents for PURY-P120
Page 1: ...Models PURY P72 P96 P120 P144T Y JMU A PURY P168 P192 P216 P240 P264 P288T Y SJMU A ...
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 36: ... II Restrictions 27 HWE09130 GB ...
Page 50: ... II Restrictions 41 41 HWE09130 GB ...
Page 67: ... 58 II Restrictions GB HWE09130 ...
Page 69: ... 60 ...
Page 95: ... 86 III Outdoor Unit Components GB HWE09130 ...
Page 97: ... 88 ...
Page 105: ... 96 IV Remote Controller GB HWE09130 ...
Page 107: ... 98 ...
Page 125: ... 116 ...
Page 145: ... 136 ...
Page 175: ... 166 VII Control GB HWE09130 ...
Page 177: ... 168 ...
Page 203: ... 194 ...
Page 363: ... 354 IX Troubleshooting GB HWE09130 ...
Page 365: ... 356 ...