VII
Control ]
- 145 -
HWE09130
GB
-5- Bypass Control
Bypass solenoid valves (SV1a), which bypass the high- and low- pressure sides, perform the following functions.
(1) Bypass solenoid valve (SV1a) (ON = Open)
(2) Bypass solenoid valve (SV9) (ON = Open)
(3) Bypass solenoid valve (SV2) (ON = Open)
(4) Bypass solenoid valve (SV5b) (ON = Open)
Operation
SV1a
ON OFF
When each indoor unit compressor startup
ON for 4 minutes.
After the restoration of thermo or 3 minutes
after restart
ON for 4 minutes.
During cooling or heating operation with the
compressor stopped
Always ON.
Exception: OFF when 63HS1-63LS is 0.2MPa[29psi] or less
After the operation has stopped
ON for 3 minutes.
Exception: OFF when 63HS1-63LS is 0.2MPa[29psi] or less
During defrost operation
ON
While the compressor is operating at the
minimum frequency and when the low pres-
sure (63LS) drops (3 or more minutes after
compressor startup)
When low pressure (63LS) drops
below 0.23MPa[33psi].
When low pressure (63LS) ex-
ceeds 0.38MPa[55psi].
When high pressure (63HS1) rises
When 63HS1 exceeds
3.62MPa[525psi]
When 63HS1 is or below
3.43MPa[497psi] and 30 seconds
have passed
Operation
SV9
ON OFF
When high pressure (63HS1) rises during
the heating operation
When 63HS1 exceeds 3.50MPa
[507psi]
When SV5b is ON and the pressure
is 2.70MPa[391psi]or below
Others
Always OFF
Operation
SV2
ON OFF
When high pressure (63HS1) rises during
the heating operation
When SV5b is OFF and the pres-
sure is 3.50MPa[507psi]or below
When 63HS1 exceeds 2.70MPa
[391psi]
When startup or resuming operation after a
defrost cycle
OFF
During defrost cycle
ON
Others
Always OFF
*P72, P96 only
Operation
SV5b
ON OFF
When high pressure (63HS1) rises during
the heating operation
When SV2 is OFF and the pressure
is 2.70MPa[391psi]or below *
When SV9 is ON and the pressure
is 3.50MPa[507psi]or below
At startup
ON
During defrost cycle
ON (open)
When returning to normal operation after
completion of the defrost cycle
ON for 5 minutes and goes OFF
Others
Always OFF
*SV2 is present only on the P72 and P96 models.
Summary of Contents for PURY-P120
Page 1: ...Models PURY P72 P96 P120 P144T Y JMU A PURY P168 P192 P216 P240 P264 P288T Y SJMU A ...
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 36: ... II Restrictions 27 HWE09130 GB ...
Page 50: ... II Restrictions 41 41 HWE09130 GB ...
Page 67: ... 58 II Restrictions GB HWE09130 ...
Page 69: ... 60 ...
Page 95: ... 86 III Outdoor Unit Components GB HWE09130 ...
Page 97: ... 88 ...
Page 105: ... 96 IV Remote Controller GB HWE09130 ...
Page 107: ... 98 ...
Page 125: ... 116 ...
Page 145: ... 136 ...
Page 175: ... 166 VII Control GB HWE09130 ...
Page 177: ... 168 ...
Page 203: ... 194 ...
Page 363: ... 354 IX Troubleshooting GB HWE09130 ...
Page 365: ... 356 ...