VIII
Test Run Mode ]
- 186 -
HWE09130
GB
Operation
Outdoor unit model
PURY-P288TSJMU-A
PURY-P144TJMU-A
PURY-P144TJMU-A
Model name of BC controller
CMB-P1016NU-HA
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
26.7°C/19.4°C [80 °F/67 °F]
Outdoor
35°C/ [95 °F/]
Indoor unit
No. of connected units
Unit
8
No. of units in operation
8
Model
-
36/36/36/36/36/36/36/36
Piping
Main pipe
m
[ft]
5 [16-3/8"]
Branch pipe
10 [32-3/4"]
Total pipe length
75 [229-5/8"]
Fan speed
-
Hi
Amount of refrigerant
kg
[lbs-oz]
46.6 [103]
Outdoor
unit
Electric current
A
71.4
Voltage
V
230
Compressor frequency
Hz
87
87
LEV open-
ing
Indoor unit
Pulse
275/275/275/275/275/275/275/275
BC controller (1/2/3)
2000/2000/290
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
2.87/0.96
[416/139]
2.87/0.96
[416/139]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.80/2.80
[406/406]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
83 [181]
83 [181]
Heat exchanger outlet
(TH3)
44 [111]
44 [111]
Accumulator inlet
10 [50]
10 [50]
Accumulator outlet
10 [50]
10 [50]
Compressor inlet
22 [72]
22 [72]
Compressor shell bottom
44 [111]
44 [111]
Indoor unit
LEV inlet
22 [72]
Heat exchanger inlet
13 [55]
Summary of Contents for PURY-P120
Page 1: ...Models PURY P72 P96 P120 P144T Y JMU A PURY P168 P192 P216 P240 P264 P288T Y SJMU A ...
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 36: ... II Restrictions 27 HWE09130 GB ...
Page 50: ... II Restrictions 41 41 HWE09130 GB ...
Page 67: ... 58 II Restrictions GB HWE09130 ...
Page 69: ... 60 ...
Page 95: ... 86 III Outdoor Unit Components GB HWE09130 ...
Page 97: ... 88 ...
Page 105: ... 96 IV Remote Controller GB HWE09130 ...
Page 107: ... 98 ...
Page 125: ... 116 ...
Page 145: ... 136 ...
Page 175: ... 166 VII Control GB HWE09130 ...
Page 177: ... 168 ...
Page 203: ... 194 ...
Page 363: ... 354 IX Troubleshooting GB HWE09130 ...
Page 365: ... 356 ...