IX
Troubleshooting ]
- 211 -
HWE09130
GB
1. Error
Code
Out-of-range outside air temperature
2. Error definition and error detection method
When the thermistor temperature of -28°C[-18°F] or below has continuously been detected for 3 minutes during heating op-
eration (during compressor operation), the unit makes an error stop and "3121" appears on the display. (Use the OC therm-
istor temperature to determine when two outdoor units are in operation.)
The compressor restarts when the thermistor temperature is -26°C[-15°F] or above (both OC and OS) during error stop. (The
error display needs to be canceled by setting the remote controller.)
Outdoor temperature error is canceled if the units stop during error stop. (The error display needs to be canceled by setting
the remote controller.)
3. Cause, check method and remedy
Check the following factors if an error is detected, without drop in the outdoor temperature.
<Reference>
3121
Cause
Check method and remedy
(1)
Thermistor failure
Check thermistor resistance.
(2)
Pinched lead wire
Check for pinched lead wire.
(3)
Torn wire coating
Check for wire coating.
(4)
A pin on the male connector is missing or
contact failure
Check connector.
(5)
Disconnected wire
Check for wire.
(6)
Thermistor input circuit failure on the control
board
Check the intake temperature of the sensor with the LED
monitor.
When the temperature is far different from the actual temper-
ature, replace the control board.
TH7
Open detection
-40 C [ -40 F ] and below (130 k )
Short detection
110 C [230 F ] and above (0.4 k )
Summary of Contents for PURY-P120
Page 1: ...Models PURY P72 P96 P120 P144T Y JMU A PURY P168 P192 P216 P240 P264 P288T Y SJMU A ...
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 36: ... II Restrictions 27 HWE09130 GB ...
Page 50: ... II Restrictions 41 41 HWE09130 GB ...
Page 67: ... 58 II Restrictions GB HWE09130 ...
Page 69: ... 60 ...
Page 95: ... 86 III Outdoor Unit Components GB HWE09130 ...
Page 97: ... 88 ...
Page 105: ... 96 IV Remote Controller GB HWE09130 ...
Page 107: ... 98 ...
Page 125: ... 116 ...
Page 145: ... 136 ...
Page 175: ... 166 VII Control GB HWE09130 ...
Page 177: ... 168 ...
Page 203: ... 194 ...
Page 363: ... 354 IX Troubleshooting GB HWE09130 ...
Page 365: ... 356 ...