[1] Functions and Factory Settings of the Dipswitches
1. Outdoor
unit
(1) Control board
1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason.
2) A: Only the switch on either the OC or OS needs to be set for the setting to be effective on both units.
B: The switches on both the OC and OS need to be set to the same setting for the setting to be effective.
C: The setting is effective for the unit on which the setting is made.
3) Refer to "VII [2] Controlling the Outdoor Unit" for details.(page 144)
4) Target evaporating temperature will change as shown in the table below each time SW2-9 is turned ON and OFF.
Switch
Function
Function according to switch setting
Switch setting timing
Units that re-
quire switch
setting
Note.2
OFF
ON
OFF
ON
OC
OS
SWU
1-2
Unit address setting
Set to 00 or 51-100 with the dial switch
Before power on
C
C
SW1
1-10
For self-diagnosis/
operation monitoring
Refer to the LED monitor display on the
outdoor unit board.
Anytime after power on
C
C
SW2
1
Centralized control
switch
Without connection
to the centralized
controller
With connection to
the centralized con-
troller
Before power on
B
B
2
Deletion of connec-
tion information
Normal control
Deletion
Before power on
A
-
3
Deletion of error his-
tory SW
(OC) Storage of IC/
OC error history
(OC) Deletion of IC/
OC error history
Anytime after power on
(When switched from OFF
to ON)
C
C
(OS) Storage of OS
error history
(OS) Deletion of
OS error history
4
Pump down mode
Normal control
Pump down mode
After being energized and
while the compressor is
stopped
A
-
5
-
-
-
-
-
-
6
-
-
-
-
-
-
7
Forced defrost
(Note 3)
Normal control
Forced defrost
starts
10 minutes
after com-
pressor
startup
Anytime af-
ter power
on (When
switched
from OFF to
ON)
A
A
8
Defrost timer setting
(Note 3)
50 minutes
90 minutes
Anytime after power on
(When switched from OFF
to ON)
B
B
9
Target evaporating
temperature setting
(Note 4)
0°C [32°F]
-2°C [28°F]
/-4°C [25°F]
/-6°C [21°F]
Anytime after power on
(When switched from OFF
to ON)
A
-
10
-
-
-
-
-
-
SW2-9
OFF
→
ON
→
OFF
→
ON
→
OFF
→
ON
Target evaporating
temperature
0
[32 ]
[32 ]
[32 ]
[25 ]
-2
[28 ]
0
0
-4
[21 ]
-6
Summary of Contents for PURY-P120
Page 1: ...Models PURY P72 P96 P120 P144T Y JMU A PURY P168 P192 P216 P240 P264 P288T Y SJMU A ...
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 36: ... II Restrictions 27 HWE09130 GB ...
Page 50: ... II Restrictions 41 41 HWE09130 GB ...
Page 67: ... 58 II Restrictions GB HWE09130 ...
Page 69: ... 60 ...
Page 95: ... 86 III Outdoor Unit Components GB HWE09130 ...
Page 97: ... 88 ...
Page 105: ... 96 IV Remote Controller GB HWE09130 ...
Page 107: ... 98 ...
Page 125: ... 116 ...
Page 145: ... 136 ...
Page 175: ... 166 VII Control GB HWE09130 ...
Page 177: ... 168 ...
Page 203: ... 194 ...
Page 363: ... 354 IX Troubleshooting GB HWE09130 ...
Page 365: ... 356 ...