IX
Troubleshooting ]
- 231 -
HWE09130
GB
1. Error
Code
Instantaneous overcurrent (Detail code 106)
Overcurrent (effective value) (Detail code 107)
2. Error definition and error detection method
P72 model
Overcurrent 94 Apeak or 22 Arms and above is detected by the current sensor.
P96, P120, P144 models
Overcurrent 94 Apeak or 35 Arms and above is detected by the current sensor.
3. Cause, check method and remedy
Refer to section -7- "Inverter (YJMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the
inverter.(page 320)
1. Error
Code
Short-circuited IPM/Ground fault (Detail code 104)
2. Error definition and error detection method
When IPM/IGBT short damage or grounding on the load side is detected just before starting the inverter.
3. Cause, check method and remedy
In the case of 4250
In the case of 4255
Refer to section -7- "Inverter" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.
4250
(YJMU-A)
Cause
Check method and remedy
(1)
Inverter output related
Refer to IX [4] -7- (2) [1] - [4].(page 322)
Check the IGBT module resistance value of the INV board, if no
problems are found.
(Refer to the Trouble shooting for IGBT module)
4250
4255
Cause
Check method and remedy
(1)
Grounding fault compressor
Refer to IX [4] -7- (2) [2].
(2)
Inverter output related
Refer to IX [4] -7- (2) [1] - [4].
Cause
Check method and remedy
(1)
Grounding fault of fan motor
Refer to IX [4] -7- (2) [5].
(2)
Fan board failure
Refer to IX [4] -7- (2) [6].
(3)
Electromagnetic contactor (52F) actuation failure
(P120, P144 only)
Check the wiring between the FAN board, 52F, and
fan motor.
Summary of Contents for PURY-P120
Page 1: ...Models PURY P72 P96 P120 P144T Y JMU A PURY P168 P192 P216 P240 P264 P288T Y SJMU A ...
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 36: ... II Restrictions 27 HWE09130 GB ...
Page 50: ... II Restrictions 41 41 HWE09130 GB ...
Page 67: ... 58 II Restrictions GB HWE09130 ...
Page 69: ... 60 ...
Page 95: ... 86 III Outdoor Unit Components GB HWE09130 ...
Page 97: ... 88 ...
Page 105: ... 96 IV Remote Controller GB HWE09130 ...
Page 107: ... 98 ...
Page 125: ... 116 ...
Page 145: ... 136 ...
Page 175: ... 166 VII Control GB HWE09130 ...
Page 177: ... 168 ...
Page 203: ... 194 ...
Page 363: ... 354 IX Troubleshooting GB HWE09130 ...
Page 365: ... 356 ...