VII
Control ]
- 148 -
HWE09130
GB
(2) Defrost operation
(3) Stopping the defrost operation
The defrost cycle ends when 12 minutes have passed since the beginning of the cycle, or when the pipe temperature (TH3)
is 10°C[50°F] or above has been continuously detected for 2 minutes.
The defrost cycle does not end for 2 minutes once started unless the pipe temperature exceeds
ǩ
below within 2 minutes.
25°C
(
ǩ
= Outdoor temperature(TH7) - 25)°C
5°C [77°F
(
ǩ
= Outdoor temperature(TH7) - 45)°F
41°F]
In the multiple-outdoor-unit system, defrosting is stopped on all units at the same time.
(4) Problems during defrost operation
If a problem is detected during defrost operation, the operation will be stopped, and the defrost prohibition time based on the
integrated compressor operation time will be set to 20 minutes.
(5) Change in the number of operating indoor units during defrost operation
Even when there is a change in the number of operating indoor units during defrost operation, the operation will continue, and
an adjustment will be made after the completion of the defrost operation.
Defrost operation will be continued, even if the indoor units stop or under the Thermo-OFF conditions until it has run its course.
Outdoou unit
Compressor frequency
Model
Compressor frequency
P72 model
60 Hz
P96 model
65 Hz
P120, P144 models
65 Hz
Outdoor unit fan
Stopped
SV1a
ON (open)
SV2
P72, P96 models
ON (open)
P120, P144 models
N/A
SV5b
ON (open)
SV5c
P72, P96 models
OFF (closed)
P120, P144 models
ON (open)
21S4a, 21S4b
OFF
SV9
OFF (closed)
BC controller
LEV1
G type: 4000, GA type: 6000
LEV3
G type: 1000, GA type: 2000
GB, HB type: 60 (full closed)
SVM1
ON
SVM2
OFF
SVM1b
ON
SVM2b
OFF
SV
B
OFF
SV
A
Ports that are connected to the indoor units in cooling Thermo-ON
Other ports : OFF
Summary of Contents for PURY-P120
Page 1: ...Models PURY P72 P96 P120 P144T Y JMU A PURY P168 P192 P216 P240 P264 P288T Y SJMU A ...
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 36: ... II Restrictions 27 HWE09130 GB ...
Page 50: ... II Restrictions 41 41 HWE09130 GB ...
Page 67: ... 58 II Restrictions GB HWE09130 ...
Page 69: ... 60 ...
Page 95: ... 86 III Outdoor Unit Components GB HWE09130 ...
Page 97: ... 88 ...
Page 105: ... 96 IV Remote Controller GB HWE09130 ...
Page 107: ... 98 ...
Page 125: ... 116 ...
Page 145: ... 136 ...
Page 175: ... 166 VII Control GB HWE09130 ...
Page 177: ... 168 ...
Page 203: ... 194 ...
Page 363: ... 354 IX Troubleshooting GB HWE09130 ...