IX
Troubleshooting ]
- 313 -
HWE09130
GB
Items to be checked
Phenomena
Remedy
[3]
Check whether
the inverter is
damaged.
(No load)
<P72 model>
1)
Inverter-related problems are de-
tected.
Connect the short-circuit con-
nector to CN6, and go to sec-
tion [1].
(1)
Disconnect the inverter
output wire from the ter-
minals of the INV board
(SC-U, SC-V, SC-W).
2)
Inverter voltage is not output.
Replace the INV board.
(2)
Disconnect the short-cir-
cuit connector from CN6
on the INV board.
3)
There is an voltage imbalance be-
tween the wires.
Greater than 5% imbalance or 5V
Replace the INV board.
(3)
Put the outdoor unit into
operation.
Check the inverter output
voltage after the inverter
output frequency has sta-
bilized.
4)
There is no voltage imbalance be-
tween the wires.
Normal
*Reconnect the short-circuit
connector to CN6 after
checking the voltage.
<P96, P120 models>
1)
Inverter-related problems are de-
tected.
Turn off SW1-1 and go to [1]
(1)
Disconnect the inverter
output wire from the out-
put terminals (U, V, W) of
the IPM.
2)
Inverter voltage is not output.
Check the connection be-
tween the IPM and the
CNIPM on the INV board.
Replace the IPM.
If the problem persists, re-
place the INV board.
(2)
Turn on SW1-1 on the
INV board.
3)
There is an voltage imbalance be-
tween the wires.
Greater than 5% imbalance or 5V
Replace the IPM.
If the problem persists, re-
place the INV board.
(3)
Put the outdoor unit into
operation.
4)
There is no voltage imbalance be-
tween the wires.
Normal
*Turn off SW1-1
[TJMU-A]
Summary of Contents for PURY-P120
Page 1: ...Models PURY P72 P96 P120 P144T Y JMU A PURY P168 P192 P216 P240 P264 P288T Y SJMU A ...
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 36: ... II Restrictions 27 HWE09130 GB ...
Page 50: ... II Restrictions 41 41 HWE09130 GB ...
Page 67: ... 58 II Restrictions GB HWE09130 ...
Page 69: ... 60 ...
Page 95: ... 86 III Outdoor Unit Components GB HWE09130 ...
Page 97: ... 88 ...
Page 105: ... 96 IV Remote Controller GB HWE09130 ...
Page 107: ... 98 ...
Page 125: ... 116 ...
Page 145: ... 136 ...
Page 175: ... 166 VII Control GB HWE09130 ...
Page 177: ... 168 ...
Page 203: ... 194 ...
Page 363: ... 354 IX Troubleshooting GB HWE09130 ...
Page 365: ... 356 ...