IX
Troubleshooting ]
- 243 -
HWE09130
GB
1. Error
Code
Faulty ACCT wiring (Detail code 120)
2. Error definition and error detection method
Presence of target current cannot be detected during the self-diagnostic operation immediately before startup.
3. Cause, check method and remedy
Refer to section -7- "Inverter (YJMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the
inverter.(page 320)
5301
(YJMU-A)
Cause
Check method and remedy
(1)
Inverter output wiring problem
Check output wiring connections.
Confirm that the U- and W-phase output cables are put through CT12
and CT22 on the INV board respectively.
(2)
Inverter failure
Refer to IX [4] -7- (2) [3], [4].(page 322)
(3)
Compressor failure
Refer to IX [4] -7- (2) [2].(page 322)