VIII
Test Run Mode ]
- 223 -
HWE09080
GB
Item
2-unit combination
PQRY-P216YSHMU-A
PQRY-P120YHMU-A
PQRY-P96YHMU-A
Model name of BC controller
CMB-P108NU-GA
Operating
conditions
Indoor temperature
DB/WB
21.1°C/- [70 °F/-]
Heat source water temperature
°C [ °F]
21.1 [70]
Heat source water flow rate
m
3
/h
G/h
gpm
5.76
[1522]
[25.4]
5.76
[1522]
[25.4]
Indoor
unit
No. of connected units
Unit
5
No. of units in operation
5
Model
36/36/48/48/48
Pipe
length
Main pipe
m [ft]
5 [16-3/8]
Branch pipe
10 [32-3/4]
Total pipe length
65 [213]
Fan speed
Hi
Refrigerant charge
kg
[lbs-oz]
26.2 [58]
Heat source
unit
Current
A
55.1
Voltage
V
230
Compressor frequency
Hz
81
81
LEV opening
Indoor unit
Pulse
332/332/406/406/406
BC controller (1/2/3)
110/110/1050
Pressure
switch
High pressure (63HS1)/
Low pressure (63LS)
MPa
[psi]
2.75/0.80
[399/116]
2.75/0.80
[399/116]
BC controller on the liquid side
(PS1)/Intermediate part (PS3)
2.72/2.40
[395/348]
Sectional
temperatures
Heat
source
unit
Discharge (TH4)
°C [ °F]
81 [178]
81 [178]
Heat exchanger outlet
5 [41]
5 [41]
Accumulator inlet
4 [39]
4 [39]
Accumulator outlet
4 [39]
4 [39]
Compressor inlet
4 [39]
4 [39]
Compressor shell bottom
40 [104]
40 [104]
Indoor
unit
LEV inlet
35 [95]
Heat exchanger inlet
70 [158]
Summary of Contents for PQHY-P120THMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 83: ... 74 ...
Page 103: ... 94 III Heat source Unit Components GB HWE09080 ...
Page 105: ... 96 ...
Page 113: ... 104 IV Remote Controller GB HWE09080 ...
Page 115: ... 106 ...
Page 131: ... 122 ...
Page 143: ... 134 VI Refrigerant Circuit GB HWE09080 ...
Page 145: ... 136 ...
Page 181: ... 172 VII Control GB HWE09080 ...
Page 183: ... 174 ...
Page 235: ... 226 ...
Page 367: ... 358 ...
Page 414: ......