IX
Troubleshooting ]
- 234 -
HWE09080
GB
1. Error
Code
High pressure fault 2 (Heat source unit)
2. Error definition and error detection method
If the pressure of 0.098MPa [14psi] or lower is registered on the pressure sensor immediately before start-up, it will trigger an
abnormal stop, and error code "1302" will be displayed.
3. Cause, check method and remedy
1. Error
Code
Refrigerant overcharge
2. Error definition and error detection method
An error can be detected by the discharge temperature superheat.
1) If the formula "TdSH
10°C [18°F]" is satisfied during operation (first detection), the heat source unit stops, goes into the 3-
minute restart mode, and starts up in three minutes.
2) If the formula "TdSH
10°C [18°F]" is satisfied again within 30 minutes of the first stoppage of the heat source unit (second
detection), the unit comes to an abnormal stop, and the error code "1500" appears.
3) If the formula "TdSH
10°C [18°F]" is satisfied 30 minutes or more after the first stoppage of the heat source unit, the same
sequence as Item "1 above (first detection) is followed.
4) For 30 minutes after the stop of the heat source unit, preliminary errors will be displayed on the LED display.
3. Cause, check method and remedy
1302
Cause
Check method and remedy
(1)
Inner pressure drop due to a leakage.
Refer to the page on the troubleshooting of the high
pressure sensor.(page 306)
(2)
Pressure sensor failure
(3)
Shorted-circuited pressure sensor cable due to torn
outer rubber
(4)
A pin on the male connector on the pressure sensor
is missing or contact failure
(5)
Disconnected pressure sensor cable
(6)
Failure of the pressure sensor input circuit on the
controller board
1500
Cause
Check method and remedy
(1)
Overcharged refrigerant
Refer to the page on refrigerant amount
evaluation.(page 177)
(2)
Thermistor input circuit failure on the control board
Check the temperature and pressure readings on the sen-
sor that are displayed on the LED monitor.
(3)
Faulty mounting of thermistor (TH4)
Check the temperature and pressure readings on the
thermistor that are displayed on the LED monitor.
(4)
Heat source unit LEV2a and LEV2b actuation fail-
ureHeating
Refer to the section on troubleshooting the LEV.
(page 310)
Summary of Contents for PQHY-P120THMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 83: ... 74 ...
Page 103: ... 94 III Heat source Unit Components GB HWE09080 ...
Page 105: ... 96 ...
Page 113: ... 104 IV Remote Controller GB HWE09080 ...
Page 115: ... 106 ...
Page 131: ... 122 ...
Page 143: ... 134 VI Refrigerant Circuit GB HWE09080 ...
Page 145: ... 136 ...
Page 181: ... 172 VII Control GB HWE09080 ...
Page 183: ... 174 ...
Page 235: ... 226 ...
Page 367: ... 358 ...
Page 414: ......