IX
Troubleshooting ]
- 244 -
HWE09080
GB
1. Error
Code
Open phase
2. Error definition and error detection method
An open phase of the power supply (L1 phase, L2 phase) was detected at power on.
The L3 phase current is outside of the specified range.
The open phase of the power supply may not always be detected if a power voltage from another circuit is applied.
3. Cause, check method and remedy
4102
(THMU-A)
Cause
Check method and remedy
(1)
Power supply problem
Open phase voltage of the power supply
Power supply voltage drop
Check the input voltage to the power supply terminal block TB1.
(2)
Noise filter problem
Coil problem
Circuit board failure
Check the coil connections.
Check for coil burnout.
Confirm that the voltage at the CN02 connector is 188 V or
above.
(3)
Wiring failure
Confirm that the voltage at the control board connector CNAC is
188 V or above.
If the voltage is below 188V, check the wiring connection between
the noise filter board CN02 and control board CNAC.
Confirm that the wiring between TB23 and INV board SC-T is put
through CT3.
(4)
Blown fuse
Check that F01 on the control board is not blown.
->If a blown fuse is found, check for a short-circuiting or earth fault
of the actuator.
(5)
CT3 failure
Replace the inverter if this problem is detected after the compres-
sor has gone into operation.
(6)
Control board failure
Replace the control board if none of the above is causing the
problem.
Summary of Contents for PQHY-P120THMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 83: ... 74 ...
Page 103: ... 94 III Heat source Unit Components GB HWE09080 ...
Page 105: ... 96 ...
Page 113: ... 104 IV Remote Controller GB HWE09080 ...
Page 115: ... 106 ...
Page 131: ... 122 ...
Page 143: ... 134 VI Refrigerant Circuit GB HWE09080 ...
Page 145: ... 136 ...
Page 181: ... 172 VII Control GB HWE09080 ...
Page 183: ... 174 ...
Page 235: ... 226 ...
Page 367: ... 358 ...
Page 414: ......