8-step demand control (When SW4-4 is set to ON on two heat source units)
Demand capacity is shown below.
*1. The heat source units whose SW4-4 is set to ON are designated as No. 1and No. 2 in the order of address from small to
large.
Ex) When heat source units whose SW4-4 is set to ON are designated as OS1 and OS2, OS1=No. 1 and OS2=No. 2.
12-step demand control (When SW4-4 is set to ON on three heat source units)
Demand capacity is shown below.
*1. The heat source units whose SW4-4 is set to ON are designated as No. 1, No. 2, and No. 3 in the order of address from
small to large.
Ex) When heat source units whose SW4-4 is set to ON are designated as OC, OS1, and OS2, OC=No. 1, OS1=No. 2,
and OS2=No. 3.
8-step demand
No.2 CN3D
1-2P
Open
Short-circuit
No.1 CN3D
1-2P
1-3P
Open
Short-circuit
Open
Short-circuit
Open
Open
100%
50%
88%
75%
Short-circuit
50%
0%
38%
25%
Short-circuit
Open
88%
38%
75%
63%
Short-circuit
75%
25%
63%
50%
12-step
demand
No.2 CN3D
1-2P
Open
1-3P
Open
Short-circuit
No.3 CN3D
1-2P
Open
Short-circuit
Open
Short-circuit
No.1
CN3D
1-2P
1-3P
Open
Short-
circuit
Open
Short-
circuit
Open
Short-
circuit
Open
Short-
circuit
Open
Open
100%
67%
92%
84%
67%
34%
59%
50%
Short-
circuit
67%
34%
59%
50%
34%
0%
25%
17%
Short-circuit
Open
92%
59%
84%
75%
59%
25%
50%
42%
Short-
circuit
84%
50%
75%
67%
50%
17%
42%
34%
12-step
demand
No.2 CN3D
1-2P
Short-circuit
1-3P
Open
Short-circuit
No.3 CN3D
1-2P
Open
Short-circuit
Open
Short-circuit
No.1
CN3D
1-2P
1-3P
Open
Short-
circuit
Open
Short-
circuit
Open
Short-
circuit
Open
Short-
circuit
Open
Open
92%
59%
84%
75%
84%
50%
75%
67%
Short-
circuit
59%
25%
50%
42%
50%
17%
42%
34%
Short-circuit
Open
84%
50%
75%
67%
75%
42%
67%
59%
Short-
circuit
75%
42%
67%
59%
67%
34%
59%
50%
Summary of Contents for PQHY-P120THMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 83: ... 74 ...
Page 103: ... 94 III Heat source Unit Components GB HWE09080 ...
Page 105: ... 96 ...
Page 113: ... 104 IV Remote Controller GB HWE09080 ...
Page 115: ... 106 ...
Page 131: ... 122 ...
Page 143: ... 134 VI Refrigerant Circuit GB HWE09080 ...
Page 145: ... 136 ...
Page 181: ... 172 VII Control GB HWE09080 ...
Page 183: ... 174 ...
Page 235: ... 226 ...
Page 367: ... 358 ...
Page 414: ......