VIII
Test Run Mode ]
- 195 -
HWE09080
GB
Item
2-unit combination
PQHY-P240YSHMU-A
PQHY-P120YHMU-A
PQHY-P120YHMU-A
Operating
conditions
Indoor temperature
DB/WB
26.7°C/19.4°C[80°F/67°F]
Heat source water temperature
°C [ °F]
29.4[85]
Heat source water flow rate
m
3
/h
G/h
gpm
5.76
[1522]
[25.4]
5.76
[1522]
[25.4]
Indoor
unit
No. of connected units
Unit
6
No. of units in operation
6
Model
-
36/36/36/36/48/48
Pipe
length
Main pipe
m [ft]
5 [16-3/8]
Branch pipe
10 [32-3/4]
Total pipe length
65 [213]
Fan speed
-
Hi
Refrigerant charge
kg
[lbs-oz]
26.2 [58]
Heat source
unit
Current
A
32.7
Voltage
V
230
Compressor frequency
Hz
105
105
LEV opening
Indoor unit
Pulse
325/325/325/325/387/387
SC (LEV1)
159
159
LEV2
1400
1400
Pressure
switch
High pressure (after O/S)/
Low pressure (before accumulator)
MPa
[psi]
2.30/0.81 [334/117]
2.30/0.81 [334/117]
Sectional
temperatures
Heat
source
unit
Discharge (TH4)
°C [°F]
65 [149]
65 [149]
Heat exchanger outlet
35 [95]
35 [95]
Accumulator inlet
8 [46]
8 [46]
Accumulator outlet
8 [46]
8 [46]
Compressor inlet
19 [66]
19 [66]
Compressor shell bottom
42 [108]
40 [104]
Indoor
unit
LEV inlet
19 [66]
Heat exchanger outlet
6 [43]
Summary of Contents for PQHY-P120THMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 83: ... 74 ...
Page 103: ... 94 III Heat source Unit Components GB HWE09080 ...
Page 105: ... 96 ...
Page 113: ... 104 IV Remote Controller GB HWE09080 ...
Page 115: ... 106 ...
Page 131: ... 122 ...
Page 143: ... 134 VI Refrigerant Circuit GB HWE09080 ...
Page 145: ... 136 ...
Page 181: ... 172 VII Control GB HWE09080 ...
Page 183: ... 174 ...
Page 235: ... 226 ...
Page 367: ... 358 ...
Page 414: ......