VIII
Test Run Mode ]
- 210 -
HWE09080
GB
Item
3-unit combination
PQHY-P360YSHMU-A
PQHY-
P120YHMU-A
PQHY-
P120YHMU-A
PQHY-
P120YHMU-A
Operating
conditions
Indoor temperature
DB/WB
21.1°C/- [70°F/-]
Heat source water temperature
°C [°F]
21.1 [70]
Heat source water flow rate
m3/h
G/h
gpm
5.76
[1522]
[25.4]
5.76
[1522]
[25.4]
5.76
[1522]
[25.4]
Indoor
unit
No. of connected units
Unit
7
No. of units in opera-
tion
7
Model
-
54/54/54/54/48/48/48
Pipe
length
Main pipe
m [ft]
5 [16-3/8]
Branch pipe
10 [32-3/4]
Total pipe length
75 [246-1/16]
Fan speed
-
Hi
Refrigerant charge
kg
[lbs-oz]
26.8 [60]
Heat source
unit
Current
A
84.3
Voltage
V
230
Compressor frequency
Hz
90
90
90
LEV opening
Indoor unit
Pulse
414/414/414/414/406/406/406
SC (LEV1)
0
LEV2
1400
1400
1400
Pressure
switch
High pressure (after O/S)/
Low pressure (before accumu-
lator)
MPa
[psi]
2.68/0.80
2.68/0.80
2.68/0.80
[389/116]
[389/116]
[389/116]
Sectional
temperatures
Heat
source
unit
Discharge (TH4)
°C [°F]
81 [178]
81 [178]
81 [178]
Heat exchanger outlet
5 [41]
5 [41]
5 [41]
Accumulator inlet
4 [39]
4 [39]
4 [39]
Accumulator outlet
4 [39]
4 [39]
4 [39]
Compressor inlet
4 [39]
4 [39]
4 [39]
Compressor shell bot-
tom
40 [104]
40 [104]
40 [104]
Indoor
unit
LEV inlet
39 [102]
Heat exchanger inlet
70 [158]
Summary of Contents for PQHY-P120THMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 83: ... 74 ...
Page 103: ... 94 III Heat source Unit Components GB HWE09080 ...
Page 105: ... 96 ...
Page 113: ... 104 IV Remote Controller GB HWE09080 ...
Page 115: ... 106 ...
Page 131: ... 122 ...
Page 143: ... 134 VI Refrigerant Circuit GB HWE09080 ...
Page 145: ... 136 ...
Page 181: ... 172 VII Control GB HWE09080 ...
Page 183: ... 174 ...
Page 235: ... 226 ...
Page 367: ... 358 ...
Page 414: ......